Standards
IEEE & ANSI C57 12.00,IEEE & ANSI C57 12.20, IEEE & ANSI C57 12.90
Product range
◆kVA:10 through 500
◆Temperature rise:65℃
◆Cooling type:ONAN
◆Single phase-Hert:60&50-Polarity:Additive or subtractive
◆Primary voltage:2400V through 34500GrdY/19920V
◆Secondary voltage: 120/240v,240/480V,139/277V,600V
◆Taps:+2X2.5% HV side
Technical Parameters
| Rated Capacit (kVA) |
High Voltage (V) |
Low Voltage (V) |
Loss(W) | Dimension(mm) | Weight(kg) | |||
| No-load Loss | On-load Loss | W | D | H | ||||
| 5 | 34500/19920 13800/7957 13200/7620 12470/7200 or others |
120-240 240-480 347-600 |
19 | 75 | 465 | 485 | 855 | 92 |
| 10 | 36 | 120 | 500 | 525 | 885 | 150 | ||
| 15 | 50 | 195 | 520 | 565 | 905 | 210 | ||
| 25 | 80 | 290 | 560 | 590 | 935 | 258 | ||
| 37.5 | 105 | 360 | 610 | 625 | 935 | 340 | ||
| 50 | 135 | 500 | 635 | 675 | 1035 | 395 | ||
| 75 | 190 | 650 | 745 | 840 | 1035 | 480 | ||
| 100 | 210 | 850 | 770 | 965 | 1135 | 530 | ||
| 167 | 350 | 1410 | 795 | 890 | 1335 | 680 | ||






Reviews