{"id":2873,"date":"2026-08-27T15:58:00","date_gmt":"2026-08-27T15:58:00","guid":{"rendered":"https:\/\/lbajiele.com\/?p=2873"},"modified":"2026-08-25T12:10:06","modified_gmt":"2026-08-25T12:10:06","slug":"buck-boost-transformer-guide","status":"publish","type":"post","link":"https:\/\/lbajiele.com\/ar\/blog\/buck-boost-transformer-guide\/","title":{"rendered":"\u0645\u062d\u0648\u0644 \u062e\u0641\u0636 \u0648\u0631\u0641\u0639 \u0627\u0644\u062c\u0647\u062f: \u062f\u0644\u064a\u0644 \u0627\u0644\u062d\u062c\u0645 \u0648\u0627\u0644\u062a\u0648\u0635\u064a\u0644 \u0648\u0627\u0644\u062a\u0637\u0628\u064a\u0642"},"content":{"rendered":"<p><strong>A buck-boost transformer makes a relatively small voltage correction by adding or subtracting a winding voltage, often in an autotransformer connection; it can correct 208 V toward 230\/240 V or reduce a slightly high supply, but it normally does not provide isolation.<\/strong> Selection requires input voltage, desired output, phase, load kVA or amperes, connection and continuous duty. A wiring diagram is model- and application-specific and must come from the manufacturer.<\/p>\n<div class=\"lbaji-key-takeaways\"><h2>\u0627\u0644\u0646\u0642\u0627\u0637 \u0627\u0644\u0631\u0626\u064a\u0633\u064a\u0629<\/h2><ul><li>Size from voltage difference and load current, not total load kVA alone.<\/li><li>Autotransformer connections do not provide galvanic isolation.<\/li><li>Confirm motor voltage range, grounding and exact manufacturer diagram.<\/li><\/ul><\/div>\n<h2>How Bucking and Boosting Works<\/h2><figure class=\"wp-block-image size-large\"><img decoding=\"async\" alt=\"Dry-type isolation and buck-boost transformers\" loading=\"lazy\" src=\"https:\/\/lbajiele.com\/wp-content\/uploads\/2026\/08\/dry-type-isolation-transformers.png\"\/><figcaption>Dry-type isolation and buck-boost transformers.<\/figcaption><\/figure>\n<p>A small secondary winding is connected in series with the supply. With additive polarity, its voltage raises the load voltage; with subtractive polarity, it lowers the load voltage. Reversing the series connection changes boost to buck, but the exact terminals depend on the product diagram.<\/p>\n<p>In an autotransformer connection, part of the power transfers conductively and only the correction portion is transformed magnetically. This allows a small nameplate transformer to support a larger load kVA for a modest voltage change.<\/p>\n<h2>Sizing from Load Current and Voltage Difference<\/h2>\n<p>The transformed kVA is approximately correction volts \u00d7 load amperes \u00f7 1,000 for single phase. For example, correcting 208 V to 236 V at 40 A requires about 28 \u00d7 40 \u00f7 1,000 = 1.12 kVA of transformed capacity, subject to the manufacturer selection table and connection.<\/p>\n<p>Do not use the load kVA as the buck-boost nameplate requirement without applying the approved method. Continuous load, motor starting, ambient and enclosure can change the final choice.<\/p>\n<h2>Single-Phase and Three-Phase Connections<\/h2><figure class=\"wp-block-image size-large\"><img decoding=\"async\" alt=\"Transformer voltage testing\" loading=\"lazy\" src=\"https:\/\/lbajiele.com\/wp-content\/uploads\/2026\/08\/control-transformer-voltage-testing.png\"\/><figcaption>Transformer voltage testing.<\/figcaption><\/figure>\n<p>Single-phase applications may use one unit with a series connection. Three-phase correction commonly uses two or three units depending on open-delta or wye arrangements and load conditions. Unequal single-phase loading or four-wire systems require careful neutral and connection review.<\/p>\n<p>The manufacturer diagram specifies primary winding series\/parallel links and series-winding polarity. An incorrect link can produce the wrong voltage or a short circuit.<\/p>\n<h2>Buck-Boost Selection Examples<\/h2><figure class=\"wp-block-table is-style-stripes\"><table><thead><tr><th scope=\"col\">Input<\/th><th scope=\"col\">Target<\/th><th scope=\"col\">Load current<\/th><th scope=\"col\">Correction<\/th><th scope=\"col\">Approx. transformed kVA<\/th><\/tr><\/thead><tbody><tr><td>\u0662\u0660\u0668 \u0641\u0648\u0644\u0637<\/td><td>236 V<\/td><td>40 A<\/td><td>+28 V<\/td><td>1.12 kVA<\/td><\/tr><tr><td>\u0662\u0660\u0668 \u0641\u0648\u0644\u0637<\/td><td>230 V<\/td><td>60 A<\/td><td>+22 V<\/td><td>1.32 kVA<\/td><\/tr><tr><td>240 V<\/td><td>220 V<\/td><td>30 A<\/td><td>\u221220 V<\/td><td>0.60 kVA<\/td><\/tr><tr><td>230 V<\/td><td>240 V<\/td><td>50 A<\/td><td>+10 V<\/td><td>0.50 kVA<\/td><\/tr><tr><td>Note<\/td><td>\u2014<\/td><td>\u2014<\/td><td>\u2014<\/td><td>Use manufacturer tables for final selection<\/td><\/tr><\/tbody><\/table><\/figure>\n<h2>Application Limits and Alternatives<\/h2>\n<p>Buck-boost units are useful when supply voltage is consistently offset by a modest amount. They are not voltage regulators for a widely varying source, and ordinary connections do not correct phase imbalance or waveform problems.<\/p>\n<p>Choose an isolation transformer when galvanic separation, separately derived grounding or larger ratio change is required. Use a regulator, tap-changing transformer or power-electronic solution where voltage changes dynamically.<\/p>\n<h2>\u0627\u0644\u062a\u062d\u0642\u0642 \u0627\u0644\u0647\u0646\u062f\u0633\u064a \u0648\u062d\u062f\u0648\u062f \u0627\u0644\u0623\u0645\u0627\u0646<\/h2><p>\u064a\u0648\u0641\u0631 \u0647\u0630\u0627 \u0627\u0644\u062f\u0644\u064a\u0644 \u062f\u0639\u0645\u0627\u064b \u0644\u0644\u0645\u0648\u0627\u0635\u0641\u0627\u062a \u0648\u0627\u0644\u0645\u0634\u062a\u0631\u064a\u0627\u062a\u061b \u0648\u0647\u0648 \u0644\u0627 \u064a\u063a\u0646\u064a \u0639\u0646 \u062f\u0631\u0627\u0633\u0629 \u0627\u0644\u0645\u0634\u0631\u0648\u0639\u060c \u0623\u0648 \u0627\u0644\u0643\u0648\u062f \u0627\u0644\u0645\u0639\u0645\u0648\u0644 \u0628\u0647\u060c \u0623\u0648 \u062a\u0639\u0644\u064a\u0645\u0627\u062a \u0627\u0644\u0645\u0635\u0646\u0639\u060c \u0623\u0648 \u0623\u0639\u0645\u0627\u0644 \u0637\u0627\u0642\u0645 \u0627\u0644\u0643\u0647\u0631\u0628\u0627\u0621 \u0627\u0644\u0645\u0624\u0647\u0644. \u062a\u062d\u0642\u0642 \u0645\u0645\u0651\u0627 \u064a\u0644\u064a \u0642\u0628\u0644 \u0627\u062e\u062a\u064a\u0627\u0631 \u0627\u0644\u0645\u0639\u062f\u0627\u062a\u060c \u0623\u0648 \u0627\u062e\u062a\u0628\u0627\u0631\u0647\u0627\u060c \u0623\u0648 \u062a\u0648\u0635\u064a\u0644 \u0623\u0633\u0644\u0627\u0643\u0647\u0627\u060c \u0623\u0648 \u062a\u0634\u063a\u064a\u0644\u0647\u0627:<\/p><ul><li>Measure worst-case source voltage under representative loading.<\/li><li>Confirm load voltage tolerance, starting current and continuous duty.<\/li><li>Verify that lack of isolation is acceptable for grounding and safety.<\/li><li>Use only the exact manufacturer wiring diagram for the selected model.<\/li><li>Check overcurrent protection, conductor ampacity and enclosure environment.<\/li><\/ul>\n<h2>\u0627\u0644\u0645\u0639\u0644\u0648\u0645\u0627\u062a \u0627\u0644\u0645\u0631\u0627\u062f \u062a\u0636\u0645\u064a\u0646\u0647\u0627 \u0641\u064a \u0637\u0644\u0628 \u0639\u0631\u0636 \u0627\u0644\u0623\u0633\u0639\u0627\u0631<\/h2><p>\u064a\u062c\u0628 \u0623\u0646 \u062a\u0633\u062a\u0646\u062f \u0623\u064a \u0639\u0631\u0636 \u0623\u0633\u0639\u0627\u0631 \u0645\u0641\u064a\u062f \u0625\u0644\u0649 \u0646\u0641\u0633 \u0627\u0644\u062d\u062f\u0648\u062f \u0627\u0644\u062a\u0642\u0646\u064a\u0629 \u0644\u0643\u0644 \u0645\u064f\u0648\u0631\u0650\u0651\u062f. \u062a\u0636\u0645\u064a\u0646 \u0627\u0644\u0645\u0639\u0644\u0648\u0645\u0627\u062a \u0627\u0644\u062a\u0627\u0644\u064a\u0629 \u0648\u0645\u0637\u0627\u0644\u0628\u0629 \u0628\u0630\u0643\u0631 \u062c\u0645\u064a\u0639 \u0627\u0644\u0627\u0646\u062d\u0631\u0627\u0641\u0627\u062a \u0635\u0631\u0627\u062d\u0629\u064b:<\/p><ul><li>Measured minimum\/maximum input and required output voltage.<\/li><li>Phase, frequency, load amperes\/kVA and motor-starting duty.<\/li><li>Required buck or boost amount and acceptable regulation.<\/li><li>Grounding, neutral, isolation and enclosure requirements.<\/li><li>Connection diagram, taps, protection, dimensions and test data.<\/li><\/ul>\n<h2>\u0645\u0646 \u0627\u0644\u0628\u064a\u0627\u0646\u0627\u062a \u0627\u0644\u0641\u0646\u064a\u0629 \u0625\u0644\u0649 \u0642\u0631\u0627\u0631 \u0645\u0639\u062a\u0645\u062f<\/h2><p>Use a staged review rather than approving the first catalogue match. Begin with how bucking and boosting works, then reconcile sizing from load current and voltage difference with single-phase and three-phase connections. Complete the review with application limits and alternatives. At each stage, record the source document, units, operating case and person responsible for approval. This prevents a value copied from an old drawing, nominal system label or unrelated product from becoming an uncontrolled design input.<\/p><p>\u0642\u0628\u0644 \u0627\u0644\u0642\u0628\u0648\u0644\u060c \u0642\u0627\u0631\u0646 \u0627\u0633\u062a\u062c\u0627\u0628\u0629 \u0627\u0644\u0645\u0648\u0631\u062f \u0628\u0646\u062f\u0627\u064b \u0628\u0646\u062f\u0627\u064b \u0645\u0639 \u0637\u0644\u0628 \u062a\u0642\u062f\u064a\u0645 \u0627\u0644\u0642\u062d\u0648\u0635\u0627\u062a \u0648\u062d\u062f\u062f \u0643\u0644 \u0627\u0633\u062a\u062b\u0646\u0627\u0621. \u062a\u0623\u0643\u062f \u0645\u0646 \u0623\u0646 \u0627\u0644\u0631\u0633\u0648\u0645\u0627\u062a\u060c \u0648\u0627\u0644\u062d\u0633\u0627\u0628\u0627\u062a\u060c \u0648\u0627\u0644\u0625\u0639\u062f\u0627\u062f\u0627\u062a\u060c \u0648\u0627\u0644\u0634\u0647\u0627\u062f\u0627\u062a\u060c \u0648\u062a\u0642\u0627\u0631\u064a\u0631 \u0627\u0644\u0627\u062e\u062a\u0628\u0627\u0631 \u062a\u0634\u064a\u0631 \u0625\u0644\u0649 \u0627\u0644\u0637\u0631\u0627\u0632 \u0648\u0627\u0644\u0645\u0631\u0627\u062c\u0639\u0629 \u0627\u0644\u0645\u0642\u062f\u0645\u064a\u0646 \u0628\u062f\u0642\u0629. \u0627\u062d\u062a\u0641\u0638 \u0628\u0627\u0644\u0648\u062b\u0627\u0626\u0642 \u0627\u0644\u0645\u0642\u062f\u0645\u0629 \u0627\u0644\u0645\u0639\u062a\u0645\u062f\u0629\u060c \u0648\u0628\u064a\u0627\u0646\u0627\u062a \u0644\u0648\u062d\u0629 \u0627\u0644\u0627\u0633\u0645\u060c \u0648\u0646\u062a\u0627\u0626\u062c \u0627\u0644\u0645\u0635\u0646\u0639\u060c \u0648\u0642\u064a\u0627\u0633\u0627\u062a \u0627\u0644\u062a\u0634\u063a\u064a\u0644 \u0643\u062e\u0637 \u0623\u0633\u0627\u0633 \u0644\u0644\u0635\u064a\u0627\u0646\u0629. \u0625\u0630\u0627 \u062a\u063a\u064a\u0631 \u0627\u0644\u062a\u0642\u064a\u064a\u0645\u060c \u0623\u0648 \u0627\u0644\u062a\u0648\u0635\u064a\u0644\u060c \u0623\u0648 \u0627\u0644\u0628\u064a\u0626\u0629\u060c \u0623\u0648 \u0634\u0631\u0637 \u0627\u0644\u0627\u062e\u062a\u0628\u0627\u0631\u060c \u0641\u0623\u0639\u062f \u0627\u0644\u0645\u0631\u0627\u062c\u0639\u0629 \u0627\u0644\u0645\u062a\u0623\u062b\u0631\u0629 \u0628\u062f\u0644\u0627\u064b \u0645\u0646 \u0627\u0641\u062a\u0631\u0627\u0636 \u0623\u0646 \u0627\u0644\u0627\u0633\u062a\u0646\u062a\u0627\u062c \u0627\u0644\u0623\u0635\u0644\u064a \u064a\u0638\u0644 \u0633\u0627\u0631\u064a\u0627\u064b.<\/p>\n<p>\u064a\u062c\u0628 \u0623\u0646 \u062a\u062d\u062f\u062f \u0645\u0631\u0627\u0642\u0628\u0629 \u0627\u0644\u0648\u062b\u0627\u0626\u0642 \u0627\u0644\u0645\u0631\u0627\u062c\u0639\u0629\u060c \u0648\u062d\u0627\u0644\u0629 \u0627\u0644\u0645\u0648\u0627\u0641\u0642\u0629\u060c \u0648\u0627\u0644\u0645\u0644\u0641\u0627\u062a \u0627\u0644\u0645\u0644\u063a\u0627\u0629. \u064a\u062c\u0628 \u0623\u0646 \u062a\u062a\u0644\u0642\u0649 \u0627\u0644\u0641\u0631\u0642 \u0627\u0644\u0645\u064a\u062f\u0627\u0646\u064a\u0629 \u0646\u0641\u0633 \u0627\u0644\u0642\u064a\u0645 \u0627\u0644\u0645\u0639\u062a\u0645\u062f\u0629 \u0627\u0644\u0645\u0633\u062a\u062e\u062f\u0645\u0629 \u0644\u0644\u0645\u0634\u062a\u0631\u064a\u0627\u062a\u060c \u0628\u064a\u0646\u0645\u0627 \u064a\u062c\u0628 \u0623\u0646 \u062a\u0633\u062c\u0644 \u0633\u062c\u0644\u0627\u062a \u0627\u0644\u062a\u0634\u063a\u064a\u0644 \u0627\u0644\u062a\u062c\u0631\u064a\u0628\u064a \u0623\u064a \u062a\u063a\u064a\u064a\u0631 \u0645\u0635\u0631\u062d \u0628\u0647 \u062a\u0645 \u0625\u062c\u0631\u0627\u0621\u0647 \u0623\u062b\u0646\u0627\u0621 \u0627\u0644\u062a\u0631\u0643\u064a\u0628. \u062a\u064f\u0639\u062f \u0647\u0630\u0647 \u0627\u0644\u0642\u0627\u0628\u0644\u064a\u0629 \u0644\u0644\u062a\u062a\u0628\u0639 \u0645\u0647\u0645\u0629 \u0628\u0634\u0643\u0644 \u062e\u0627\u0635 \u0639\u0646\u062f\u0645\u0627 \u064a\u062a\u0645 \u0627\u0633\u062a\u0628\u062f\u0627\u0644 \u0627\u0644\u0645\u0639\u062f\u0627\u062a \u0628\u0639\u062f \u0633\u0646\u0648\u0627\u062a: \u0641\u0627\u0644\u0645\u0647\u0646\u062f\u0633 \u0627\u0644\u062a\u0627\u0644\u064a \u064a\u062d\u062a\u0627\u062c \u0625\u0644\u0649 \u0648\u0627\u062c\u0647\u0627\u062a \u0645\u064f\u062a\u062d\u0642\u0642 \u0645\u0646\u0647\u0627 \u0648\u0633\u062c\u0644 \u0627\u062e\u062a\u0628\u0627\u0631\u0627\u062a\u060c \u0648\u0644\u064a\u0633 \u0648\u0635\u0641\u0627\u064b \u063a\u064a\u0631 \u0645\u0643\u062a\u0645\u0644 \u0645\u0646\u0642\u0648\u0644\u0627\u064b \u0645\u0646 \u0623\u0645\u0631 \u0634\u0631\u0627\u0621.<\/p>\n<h2>\u062a\u063a\u0637\u064a\u0629 \u0645\u0633\u062a\u0646\u062f\u0629 \u0625\u0644\u0649 \u0646\u062a\u0627\u0626\u062c \u0627\u0644\u0628\u062d\u062b \u0627\u0644\u062d\u0627\u0644\u064a\u0629<\/h2><p>The current U.S. Google top-20 review repeatedly surfaced themes including What is a buck-boost transformer?, Frequency, Yinleader 5000 Step Up\/Down Transformer Converter 110\/120Volt-220\/240Volt | US Power Cord,Circuit Breaker Protection (Grey), Buck-Boost Transformers in Different Systems, Acme Electric T181054 Buck-Boost Transformer, Single Phase, 120 x 240 Primary Volts &#8211; 16\/32 Secondary Volts, 50 VA. The article addresses those user needs in an original engineering and procurement sequence; competitor brand navigation and unrelated sales material were excluded.<\/p>\n<h2>\u0627\u0644\u0645\u0648\u0627\u0631\u062f \u0630\u0627\u062a \u0627\u0644\u0635\u0644\u0629 \u0628\u0640 LBAJI<\/h2><p>\u062a\u0627\u0628\u0639 \u0645\u0639 <a href=\"https:\/\/lbajiele.com\/ar\/blog\/step-up-transformer-guide\/\">step-up transformer guide<\/a> <a href=\"https:\/\/lbajiele.com\/ar\/blog\/transformer-calculator-calculator-and-formula-guide\/\">\u062d\u0627\u0633\u0628\u0629 \u0627\u0644\u0645\u062d\u0648\u0644\u0627\u062a<\/a> <a href=\"https:\/\/lbajiele.com\/ar\/product-category\/transformer\/\">dry-type transformer products<\/a>. \u062a\u0633\u0627\u0639\u062f \u0647\u0630\u0647 \u0627\u0644\u0645\u0648\u0627\u0631\u062f \u0641\u064a \u0631\u0628\u0637 \u0627\u0644\u062d\u0633\u0627\u0628 \u0623\u0648 \u0642\u0631\u0627\u0631 \u0627\u0644\u0645\u0643\u0648\u0646 \u0628\u0645\u0648\u0627\u0635\u0641\u0627\u062a \u0643\u0627\u0645\u0644\u0629 \u0644\u0644\u0645\u062d\u0648\u0644\u060c \u0623\u0648 \u0627\u0644\u0645\u0641\u0627\u062a\u064a\u062d \u0627\u0644\u0643\u0647\u0631\u0628\u0627\u0626\u064a\u0629\u060c \u0623\u0648 \u0627\u0644\u062a\u062d\u0643\u0645\u060c \u0623\u0648 \u0627\u0644\u062a\u0648\u0632\u064a\u0639.<\/p>\n<div id=\"rank-math-faq\" class=\"rank-math-block\">\n<div class=\"rank-math-list\">\n<\/div>\n<\/div>\n<section class=\"lbaji-technical-references\"><h2>\u0627\u0644\u0645\u0631\u0627\u062c\u0639 \u0627\u0644\u0641\u0646\u064a\u0629 \u0648\u0627\u0644\u0642\u0631\u0627\u0621\u0629 \u0627\u0644\u0625\u0636\u0627\u0641\u064a\u0629<\/h2><ul><li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/588\" rel=\"noopener noreferrer nofollow\" target=\"_blank\">IEC 60076-1<\/a> \u2014 General transformer requirements.<\/li><li><a href=\"https:\/\/www.nfpa.org\/codes-and-standards\" rel=\"noopener noreferrer nofollow\" target=\"_blank\">\u0623\u0643\u0648\u0627\u062f \u0648\u0645\u0639\u0627\u064a\u064a\u0631 \u0627\u0644\u062c\u0645\u0639\u064a\u0629 \u0627\u0644\u0648\u0637\u0646\u064a\u0629 \u0644\u0644\u062d\u0645\u0627\u064a\u0629 \u0645\u0646 \u0627\u0644\u062d\u0631\u064a\u0642 (NFPA)<\/a> \u2014 Installation and protection rules.<\/li><li><a href=\"https:\/\/www.nist.gov\/pml\/owm\/si-units-electric-current-ampere\" rel=\"noopener noreferrer nofollow\" target=\"_blank\">\u0648\u062d\u062f\u0627\u062a \u0627\u0644\u0646\u0638\u0627\u0645 \u0627\u0644\u062f\u0648\u0644\u064a \u0644\u0644\u0642\u064a\u0627\u0633 \u0627\u0644\u062a\u0627\u0628\u0639\u0629 \u0644\u0644\u0645\u0639\u0647\u062f \u0627\u0644\u0648\u0637\u0646\u064a \u0627\u0644\u0645\u0639\u0627\u064a\u064a\u0631 \u0648\u0627\u0644\u062a\u0643\u0646\u0648\u0644\u0648\u062c\u064a\u0627<\/a> \u2014 Electrical unit references.<\/li><\/ul><\/section>\n<h2>\u062e\u0627\u062a\u0645\u0629<\/h2><p>Buck-boost transformers are efficient fixed voltage-correction tools when the source, target and load are well defined. Calculate transformed kVA, confirm the non-isolated grounding arrangement and follow the exact manufacturer connection diagram.<\/p>","protected":false},"excerpt":{"rendered":"<p>\u0645\u064f\u062d\u0648\u0651\u0650\u0644 \u062e\u0641\u0636\/\u0631\u0641\u0639 \u0627\u0644\u062c\u0647\u062f \u064a\u064f\u062c\u0631\u064a \u062a\u0635\u062d\u064a\u062d\u0627\u064b \u0637\u0641\u064a\u0641\u0627\u064b \u0646\u0633\u0628\u064a\u0627\u064b \u0641\u064a \u0627\u0644\u062c\u0647\u062f \u0639\u0646 \u0637\u0631\u064a\u0642 \u0625\u0636\u0627\u0641\u0629 \u0623\u0648 \u0637\u0631\u062d \u062c\u0647\u062f \u0627\u0644\u0645\u0644\u0641\u060c \u0648\u063a\u0627\u0644\u0628\u0627\u064b \u0645\u0627 \u064a\u0643\u0648\u0646 \u0641\u064a \u062a\u0648\u0635\u064a\u0644\u0629 \u0645\u062d\u0648\u0651\u0650\u0644 \u0630\u0627\u062a\u064a\u061b \u0648\u064a\u0645\u0643\u0646\u0647 \u062a\u0635\u062d\u064a\u062d \u062c\u0647\u062f 208 \u0641\u0648\u0644\u062a \u0644\u064a\u0635\u0644 \u0625\u0644\u0649 230\/240 \u0641\u0648\u0644\u062a \u0623\u0648 \u062e\u0641\u0636 \u062c\u0647\u062f \u0645\u0631\u062a\u0641\u0639 \u0642\u0644\u064a\u0644\u0627\u064b...<\/p>","protected":false},"author":6,"featured_media":2872,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[52],"tags":[61,60,64,65],"class_list":["post-2873","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-transformers","tag-distribution-transformer","tag-power-transformer","tag-three-phase-transformer","tag-transformer-sizing"],"blocksy_meta":[],"acf":[],"_links":{"self":[{"href":"https:\/\/lbajiele.com\/ar\/wp-json\/wp\/v2\/posts\/2873","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/lbajiele.com\/ar\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/lbajiele.com\/ar\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/lbajiele.com\/ar\/wp-json\/wp\/v2\/users\/6"}],"replies":[{"embeddable":true,"href":"https:\/\/lbajiele.com\/ar\/wp-json\/wp\/v2\/comments?post=2873"}],"version-history":[{"count":1,"href":"https:\/\/lbajiele.com\/ar\/wp-json\/wp\/v2\/posts\/2873\/revisions"}],"predecessor-version":[{"id":3014,"href":"https:\/\/lbajiele.com\/ar\/wp-json\/wp\/v2\/posts\/2873\/revisions\/3014"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/lbajiele.com\/ar\/wp-json\/wp\/v2\/media\/2872"}],"wp:attachment":[{"href":"https:\/\/lbajiele.com\/ar\/wp-json\/wp\/v2\/media?parent=2873"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/lbajiele.com\/ar\/wp-json\/wp\/v2\/categories?post=2873"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/lbajiele.com\/ar\/wp-json\/wp\/v2\/tags?post=2873"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}