{"id":2722,"date":"2026-08-22T14:27:00","date_gmt":"2026-08-22T14:27:00","guid":{"rendered":"https:\/\/lbajiele.com\/?p=2722"},"modified":"2026-10-23T00:44:33","modified_gmt":"2026-10-23T00:44:33","slug":"75-kva-transformer-amps-guide","status":"publish","type":"post","link":"https:\/\/lbajiele.com\/es\/blog\/75-kva-transformer-amps-guide\/","title":{"rendered":"Amperios de un transformador de 75 kVA: Gu\u00eda de corriente primaria y secundaria"},"content":{"rendered":"<p><strong>Un transformador de 75 kVA no tiene una sola clasificaci\u00f3n de amperaje fija.<\/strong> Current depends on phase and voltage: single-phase current is 75,000 \u00f7 V; three-phase line current is 75,000 \u00f7 (1.732 \u00d7 V). For example, 75 kVA is about 90.2 A at 480 V three-phase and 208.2 A at 208 V three-phase.<\/p>\n<div class=\"lbaji-key-takeaways\">\n<h2>Puntos clave<\/h2>\n<ul>\n<li>At 75 kVA, full-load amps depend on phase and the voltage at the side being measured.<\/li>\n<li>At 480 V three phase the result is 90.2 A; at 208 V three phase it is 208.2 A.<\/li>\n<li>These are winding current calculations, not automatic breaker, cable, or safe continuous-load ratings.<\/li>\n<\/ul>\n<\/div>\n<h2>F\u00f3rmula de corriente de 75 kVA<\/h2>\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" alt=\"Three-phase transformer and switchboard used for full-load current calculations\" loading=\"lazy\" src=\"https:\/\/lbajiele.com\/wp-content\/uploads\/2026\/08\/three-phase-kva-to-amps.png\"\/><figcaption>Transformador trif\u00e1sico y cuadro el\u00e9ctrico utilizados para los c\u00e1lculos de corriente a plena carga.<\/figcaption><\/figure>\n<p>Para monof\u00e1sica, I = kVA \u00d7 1.000 \u00f7 V. Para trif\u00e1sica, I = kVA \u00d7 1.000 \u00f7 (\u221a3 \u00d7 tensi\u00f3n entre fases). Utilice la tensi\u00f3n de placa en lugar de un valor nominal estimado. Estas ecuaciones describen la corriente aparente a plena carga; el dimensionamiento de los conductores y dispositivos de protecci\u00f3n sigue rigi\u00e9ndose por el c\u00f3digo aplicable, el r\u00e9gimen de carga, la temperatura y el m\u00e9todo de instalaci\u00f3n.<\/p>\n<section class=\"lbaji-article-table\">\n<h2>Tabla de comparaci\u00f3n r\u00e1pida y selecci\u00f3n<\/h2>\n<p>Utilice esta tabla como un repaso r\u00e1pido de las principales decisiones de ingenier\u00eda y adquisiciones explicadas en el art\u00edculo.<\/p>\n<figure class=\"wp-block-table is-style-stripes\" style=\"overflow-x:auto;max-width:100%\">\n<table>\n<thead>\n<tr>\n<th scope=\"col\">\u00c1rea de decisi\u00f3n<\/th>\n<th scope=\"col\">Significado pr\u00e1ctico<\/th>\n<th scope=\"col\">Qu\u00e9 verificar<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>F\u00f3rmula de corriente de 75 kVA<\/td>\n<td>Para monof\u00e1sica, I = kVA \u00d7 1.000 \u00f7 V.<\/td>\n<td>Para trif\u00e1sica, I = kVA \u00d7 1.000 \u00f7 (\u221a3 \u00d7 voltaje de l\u00ednea a l\u00ednea).<\/td>\n<\/tr>\n<tr>\n<td>Corrientes a plena carga comunes de 75 kVA<\/td>\n<td>A 240 V monof\u00e1sica, la corriente calculada es de 312,5 A, y a 480 V monof\u00e1sica es de 156,3 A.<\/td>\n<td>For three phase, common results are 90.2 A at 480 V, 104.3 A at 415 V, 108.3 A at 400 V, 208.2 A at 208 V and 180.4 A at 240 V.<\/td>\n<\/tr>\n<tr>\n<td>Amplificadores primarios y secundarios<\/td>\n<td>Una unidad trif\u00e1sica de 480 a 208Y\/120 V transporta unos 90 A en el lado de 480 V y 208 A en el lado de 208 V a 75 kVA.<\/td>\n<td>El transformador cambia la relaci\u00f3n tensi\u00f3n-corriente mientras que la potencia aparente permanece aproximadamente constante, excluyendo las p\u00e9rdidas.<\/td>\n<\/tr>\n<tr>\n<td>Dimensionamiento de interruptores y conductores<\/td>\n<td>No seleccione los disyuntores bas\u00e1ndose \u00fanicamente en el valor de plena carga.<\/td>\n<td>Los c\u00f3digos permiten o exigen disposiciones espec\u00edficas de protecci\u00f3n exclusiva principal o principal y secundaria, y tienen en cuenta la corriente de irrupci\u00f3n.<\/td>\n<\/tr>\n<tr>\n<td>\u00bfEs 75 kVA lo suficientemente grande?<\/td>\n<td>Sume los kVA de carga en lugar de simplemente sumar los amperios a trav\u00e9s de diferentes voltajes.<\/td>\n<td>Considere la demanda, el arranque de motores, los arm\u00f3nicos no lineales, la expansi\u00f3n futura, la temperatura ambiente y la regulaci\u00f3n de voltaje aceptable.<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/figure>\n<\/section>\n<h2>Corrientes a plena carga comunes de 75 kVA<\/h2>\n<p>At 240 V single phase the calculated current is 312.5 A, and at 480 V single phase it is 156.3 A. For three phase, common results are 90.2 A at 480 V, 104.3 A at 415 V, 108.3 A at 400 V, 208.2 A at 208 V and 180.4 A at 240 V. Rounding should not be used to conceal a voltage mismatch.<\/p>\n<h2>Amplificadores primarios y secundarios<\/h2>\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" alt=\"Coordinated transformer primary and secondary protection\" loading=\"lazy\" src=\"https:\/\/lbajiele.com\/wp-content\/uploads\/2026\/08\/transformer-breaker-fuse-sizing.png\"\/><figcaption>Protecci\u00f3n coordinada de primario y secundario de transformador.<\/figcaption><\/figure>\n<p>Una unidad trif\u00e1sica de 480 a 208Y\/120 V transporta unos 90 A en el lado de 480 V y 208 A en el lado de 208 V a 75 kVA. El transformador cambia la relaci\u00f3n entre tensi\u00f3n y corriente mientras que la potencia aparente permanece aproximadamente constante, excluyendo las p\u00e9rdidas. Por lo tanto, los conductores primarios y secundarios necesitan diferentes ampacidades y protecci\u00f3n.<\/p>\n<h2>Dimensionamiento de interruptores y conductores<\/h2>\n<p>No seleccione interruptores bas\u00e1ndose \u00fanicamente en la cifra de plena carga. Los c\u00f3digos permiten o exigen disposiciones de protecci\u00f3n espec\u00edficas solo en el primario o en el primario y secundario, y tienen en cuenta la corriente de conexi\u00f3n. Los conductores deben comprobarse en cuanto a carga continua, temperatura del aislamiento, valores nominales de los terminales, correcci\u00f3n ambiental, agrupamiento y ca\u00edda de tensi\u00f3n. Un dise\u00f1ador cualificado debe coordinar los dispositivos aguas arriba y aguas abajo.<\/p>\n<h2>\u00bfEs 75 kVA lo suficientemente grande?<\/h2>\n<p>Sume kVA de carga en lugar de simplemente sumar amperios a diferentes voltajes. Considere la demanda, el arranque de motores, los arm\u00f3nicos no lineales, la expansi\u00f3n futura, la temperatura ambiente y la regulaci\u00f3n de voltaje aceptable. Una unidad que sea adecuada para una carga constante puede producir una ca\u00edda de voltaje excesiva durante la aceleraci\u00f3n del motor o calentarse en exceso con una corriente rica en arm\u00f3nicos.<\/p>\n<h2>Controles de placa de caracter\u00edsticas y adquisiciones<\/h2>\n<p>Confirme el voltaje primario y secundario, fase, frecuencia, conexi\u00f3n vectorial o de devanado, derivaciones, impedancia, clase de aislamiento, aumento de temperatura, gabinete, eficiencia, nivel de ruido y accesorios. Para modernizaciones, verifique el espacio ocupado, la entrada de cables, la disposici\u00f3n de los terminales, la corriente de falla disponible y la protecci\u00f3n aguas arriba antes de realizar el pedido.<\/p>\n<section class=\"lbaji-gsc-update\">\n<h2>75 kVA Full-Load Amps by Voltage and Phase<\/h2>\n<p>The table below uses a 75,000 VA nameplate rating. For three-phase rows, voltage means line-to-line voltage and current means line current. Single-phase rows use the voltage across the winding. Values are rounded to one decimal ampere; the design calculation should use the actual nameplate voltage and the project electrical drawings.<\/p>\n<figure class=\"wp-block-table is-style-stripes\" style=\"overflow-x:auto;max-width:100%\">\n<table>\n<thead>\n<tr>\n<th scope=\"col\">System voltage<\/th>\n<th scope=\"col\">Single-phase full-load current<\/th>\n<th scope=\"col\">Three-phase full-load line current<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>208 V<\/td>\n<td>360.6 A<\/td>\n<td>208.2 A<\/td>\n<\/tr>\n<tr>\n<td>230 V<\/td>\n<td>326.1 A<\/td>\n<td>188.3 A<\/td>\n<\/tr>\n<tr>\n<td>240 V<\/td>\n<td>312,5 A<\/td>\n<td>180.4 A<\/td>\n<\/tr>\n<tr>\n<td>400 V<\/td>\n<td>187,5 A<\/td>\n<td>108,3 A<\/td>\n<\/tr>\n<tr>\n<td>415 V<\/td>\n<td>180.7 A<\/td>\n<td>104.3 A<\/td>\n<\/tr>\n<tr>\n<td>480 V<\/td>\n<td>156.3 A<\/td>\n<td>90.2 A<\/td>\n<\/tr>\n<tr>\n<td>600 V<\/td>\n<td>125,0 A<\/td>\n<td>72.2 A<\/td>\n<\/tr>\n<\/tbody>\n<\/table><figcaption>Calculated from I = 75,000\/V for single phase and I = 75,000\/(\u221a3 \u00d7 V) for balanced three phase. Formula basis: <a href=\"https:\/\/www.se.com\/us\/en\/faqs\/FA101694\/\" target=\"_blank\" rel=\"noopener nofollow\">Schneider Electric transformer capacity FAQ<\/a> y el <a href=\"https:\/\/www.electrical-installation.org\/enwiki\/Choice_of_transformer_rating\" target=\"_blank\" rel=\"noopener nofollow\">Electrical Installation Guide<\/a>.<\/figcaption><\/figure>\n<p>This table is a current lookup, not a promise that every 75 kVA transformer is available in every listed voltage or connection. Confirm the actual primary and secondary nameplate ratings, winding connection, frequency, taps and cooling designation. Never use a 400 V row for a 480 V winding simply because both are described as industrial three-phase systems.<\/p>\n<h2>Worked Example: 480 V Primary to 208Y\/120 V Secondary<\/h2>\n<p>Consider a balanced 75 kVA, three-phase step-down transformer with a 480 V line-to-line primary and a 208Y\/120 V secondary. On the primary, the theoretical full-load line current is 75,000 \u00f7 (\u221a3 \u00d7 480) = 90.2 A. On the secondary, it is 75,000 \u00f7 (\u221a3 \u00d7 208) = 208.2 A. The 120 V marking identifies line-to-neutral voltage on the wye secondary. For the three-phase calculation, use 208 V line-to-line, not 120 V.<\/p>\n<p>The higher secondary current is expected: voltage falls while apparent power remains approximately the same, allowing for real transformer losses. When reviewing a one-line diagram, calculate each side separately. Check the transformer nameplate before ordering a breaker or cable; current alone does not establish conductor ampacity, breaker setting or short-circuit duty.<\/p>\n<h2>How Many kW Can a 75 kVA Transformer Supply?<\/h2>\n<p>kVA measures apparent power; kW measures real power. For a balanced load, estimated real power is kW = 75 \u00d7 power factor. At 0.8 power factor, that is 60 kW. At 0.9 power factor, it is 67.5 kW. At unity power factor, the mathematical maximum is 75 kW. These figures do not replace a load study: harmonics, motor starting, duty cycle, ambient temperature and the transformer&#8217;s actual thermal rating still matter.<\/p>\n<p>Do not apply an automatic \u201c80% of 75 kVA\u201d rule to every transformer. A continuous-load rule for a particular protective device or installation is not the same as the transformer&#8217;s nameplate thermal capacity. Ask the electrical designer to document the applicable code, manufacturer instructions, load profile and required spare capacity.<\/p>\n<h2>When 75 kVA Is Too Small<\/h2>\n<p>Compare the highest expected coincident demand in kVA with the transformer&#8217;s rating under the actual operating conditions. If several loads start at different times, a simple sum of every nameplate rating may overstate demand. If large motors start together, steady-state current can understate the short-duration voltage dip. Record both cases rather than treating a single amperage number as the entire sizing decision.<\/p>\n<p>For example, a balanced 480 V three-phase load drawing 100 A represents approximately \u221a3 \u00d7 480 \u00d7 100 \u00f7 1,000 = 83.1 kVA before any allowance for expansion. That exceeds 75 kVA. Conversely, a 60 A load at the same voltage represents about 49.9 kVA, leaving apparent-power headroom, subject to starting current, thermal conditions and other connected loads. Schneider Electric&#8217;s <a href=\"https:\/\/www.se.com\/us\/en\/faqs\/FA101694\/\" target=\"_blank\" rel=\"noopener nofollow\">capacity guidance<\/a> explicitly notes that motor and specialty loads may require more than the simple arithmetic result.<\/p>\n<h2>What to Send With a 75 kVA Transformer Inquiry<\/h2>\n<p>Give the supplier the primary and secondary voltage, phase, frequency, connection, installation site, required enclosure, ambient conditions and available fault current. Include the load schedule, motor-starting information, harmonic-producing equipment and space limits. Ask for a data sheet showing nameplate ratings, impedance, losses, temperature rise, dimensions and routine test documents. If replacing a unit, provide photos of the existing nameplate and terminal layout, not only the phrase \u201c75 kVA transformer.\u201d<\/p>\n<p>For adjacent calculations, use our <a href=\"https:\/\/lbajiele.com\/es\/blog\/how-much-load-can-a-63-kva-transformer-handle\/\">63 kVA load-capacity example<\/a>, <a href=\"https:\/\/lbajiele.com\/es\/blog\/amps-convert-to-kva-calculator-and-formula-guide\/\">amps-to-kVA formula guide<\/a> y <a href=\"https:\/\/lbajiele.com\/es\/blog\/guia-de-fusibles-para-transformadores\/\">gu\u00eda de fusibles para transformadores<\/a>. Review the <a href=\"https:\/\/lbajiele.com\/es\/categoria-producto\/transformer\/\">gama de productos de transformadores<\/a> for available configurations; confirm project-specific values with the manufacturer.<\/p>\n<h2>Three-Phase Transformer Video Lesson<\/h2>\n<p>For the relationship between phase voltage, line voltage and transformer connections, this NPTEL university lecture provides a useful technical introduction. The calculation table above remains the direct answer for 75 kVA current.<\/p>\n<div class=\"lbaji-video\" style=\"position:relative;padding-bottom:56.25%;height:0;overflow:hidden\"><iframe src=\"https:\/\/www.youtube-nocookie.com\/embed\/s86tXyDQIxg\" title=\"NPTEL Introduction to Three Phase Transformer\" loading=\"lazy\" allow=\"accelerometer; encrypted-media; gyroscope; picture-in-picture\" allowfullscreen style=\"position:absolute;top:0;left:0;width:100%;height:100%;border:0\"><\/iframe><\/div>\n<p><a href=\"https:\/\/www.youtube.com\/watch?v=s86tXyDQIxg\" target=\"_blank\" rel=\"noopener nofollow\">Watch NPTEL&#8217;s Introduction to Three Phase Transformer on YouTube<\/a>.<\/p>\n<\/section>\n<h2>Equipos LBAJI relacionados<\/h2>\n<p>Revisa lo pertinente <a href=\"https:\/\/lbajiele.com\/es\/categoria-producto\/transformer\/\">Gama de productos LBAJI<\/a> y el de apoyo <a href=\"https:\/\/lbajiele.com\/es\/blog\/complete-guide-to-transformer-capacity-size-dimensions\/\">Gu\u00eda de pilares sobre capacidad, tama\u00f1o y dimensiones de transformadores<\/a>. Env\u00ede el diagrama unifilar, las capacidades, la cantidad y el entorno para una configuraci\u00f3n espec\u00edfica del proyecto.<\/p>\n<section class=\"lbaji-visible-faq\" aria-label=\"Preguntas frecuentes\">\n<h2>Preguntas frecuentes<\/h2>\n<div class=\"rank-math-list-item\" id=\"faq-question-1\">\n<h3 class=\"rank-math-question\">How many amps is a 75 kVA transformer at 480 V three phase?<\/h3>\n<div class=\"rank-math-answer\">\n<p>Approximately 90.2 A at full load, calculated as 75,000 divided by 1.732 times 480.<\/p>\n<\/div>\n<\/div>\n<div class=\"rank-math-list-item\" id=\"faq-question-2\">\n<h3 class=\"rank-math-question\">How many amps is 75 kVA at 208 V three phase?<\/h3>\n<div class=\"rank-math-answer\">\n<p>Approximately 208.2 A at full load.<\/p>\n<\/div>\n<\/div>\n<div class=\"rank-math-list-item\" id=\"faq-question-3\">\n<h3 class=\"rank-math-question\">Is kVA the same as kW?<\/h3>\n<div class=\"rank-math-answer\">\n<p>No. kVA is apparent power; kW is real power and equals kVA multiplied by power factor for a balanced load.<\/p>\n<\/div>\n<\/div>\n<div class=\"rank-math-list-item\" id=\"faq-question-4\">\n<h3 class=\"rank-math-question\">Can I size the breaker exactly at full-load current?<\/h3>\n<div class=\"rank-math-answer\">\n<p>Not automatically. Transformer inrush and electrical-code protection rules must be applied.<\/p>\n<\/div>\n<\/div>\n<div class=\"rank-math-list-item\" id=\"faq-question-5\">\n<h3 class=\"rank-math-question\">Why are secondary amps higher than primary amps?<\/h3>\n<div class=\"rank-math-answer\">\n<p>A step-down transformer reduces voltage, so current rises for approximately the same apparent power.<\/p>\n<\/div>\n<\/div>\n<\/section>\n<section class=\"lbaji-decision-aid\">\n<h2>Flujo de trabajo de evaluaci\u00f3n pr\u00e1ctica<\/h2>\n<p>Para los amperios de un transformador de 75 kva, utilice un flujo de trabajo documentado en lugar de una elecci\u00f3n basada \u00fanicamente en el cat\u00e1logo. Primero, congele las entradas del sistema y los l\u00edmites operativos. A continuaci\u00f3n, compare las opciones disponibles de construcci\u00f3n o servicio con el entorno real. Luego, verifique los c\u00e1lculos, las interfaces de protecci\u00f3n y las pruebas de aceptaci\u00f3n. Finalmente, registre las desviaciones aprobadas y conserve los resultados de referencia para la puesta en servicio y el mantenimiento.<\/p>\n<ol>\n<li>Revise las corrientes a plena carga comunes de 75 kva y registre la decisi\u00f3n espec\u00edfica del proyecto.<\/li>\n<li>Revisar los amplificadores primarios y secundarios y registrar la decisi\u00f3n espec\u00edfica del proyecto.<\/li>\n<li>Revisar el dimensionamiento del disyuntor y del conductor y registrar la decisi\u00f3n espec\u00edfica del proyecto.<\/li>\n<li>\u00bfEs de 75 kva suficiente? Revise y registre la decisi\u00f3n espec\u00edfica del proyecto.<\/li>\n<\/ol>\n<\/section>\n<section class=\"lbaji-acceptance-records\">\n<h2>Registros de aceptaci\u00f3n que se deben conservar<\/h2>\n<p>Conserve la hoja de datos aprobada, los planos, la lista de desviaciones, los certificados de materiales cuando corresponda, los informes de ensayos rutinarios y especiales, los ajustes de protecci\u00f3n, los resultados de la puesta en servicio, las fotograf\u00edas y los detalles de la placa de caracter\u00edsticas final. Registre las condiciones de ensayo adem\u00e1s de los valores, ya que la temperatura, el m\u00e9todo del instrumento y la conexi\u00f3n pueden afectar a la comparaci\u00f3n. Estos documentos establecen la l\u00ednea de base utilizada para investigar alarmas posteriores, cambios de carga o deterioro. Tambi\u00e9n evitan que se soliciten equipos de repuesto a partir de una descripci\u00f3n incompleta despu\u00e9s de que cambie el personal o los proveedores.<\/p>\n<\/section>\n<section class=\"lbaji-technical-references\">\n<h2>Referencias t\u00e9cnicas y lecturas adicionales<\/h2>\n<ul>\n<li><a href=\"https:\/\/www.energy.gov\/cmei\/buildings\/distribution-transformers\" rel=\"noopener noreferrer nofollow\" target=\"_blank\">Recursos sobre transformadores de distribuci\u00f3n del Departamento de Energ\u00eda de EE. UU.<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/588\" rel=\"noopener noreferrer nofollow\" target=\"_blank\">transformadores de potencia IEC 60076-1<\/a><\/li>\n<li><a href=\"https:\/\/www.nfpa.org\/codes-and-standards\" rel=\"noopener noreferrer nofollow\" target=\"_blank\">C\u00f3digos y normas el\u00e9ctricas de la NFPA<\/a><\/li>\n<\/ul>\n<\/section>\n<h2>Conclusi\u00f3n<\/h2>\n<p>A 75 kVA transformer does not have one fixed amp rating. Current depends on phase and voltage: single-phase current is 75,000 \u00f7 V; three-phase line current is 75,000 \u00f7 (1.732 \u00d7 V). For example, 75 kVA is about 90.2 A at 480 V three-phase and 208.2 A at 208 V three-phase. Use project data and documented acceptance criteria before purchase, installation or service.<\/p>","protected":false},"excerpt":{"rendered":"<p>75 kVA transformer amps depend on voltage and phase. See single- and three-phase current charts, a 480-to-208 V example, and sizing checks.<\/p>","protected":false},"author":6,"featured_media":2721,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[52],"tags":[85,66,65],"class_list":["post-2722","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-transformers","tag-kva-calculations","tag-transformer-capacity","tag-transformer-sizing"],"blocksy_meta":[],"acf":[],"_links":{"self":[{"href":"https:\/\/lbajiele.com\/es\/wp-json\/wp\/v2\/posts\/2722","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/lbajiele.com\/es\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/lbajiele.com\/es\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/lbajiele.com\/es\/wp-json\/wp\/v2\/users\/6"}],"replies":[{"embeddable":true,"href":"https:\/\/lbajiele.com\/es\/wp-json\/wp\/v2\/comments?post=2722"}],"version-history":[{"count":6,"href":"https:\/\/lbajiele.com\/es\/wp-json\/wp\/v2\/posts\/2722\/revisions"}],"predecessor-version":[{"id":4831,"href":"https:\/\/lbajiele.com\/es\/wp-json\/wp\/v2\/posts\/2722\/revisions\/4831"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/lbajiele.com\/es\/wp-json\/wp\/v2\/media\/2721"}],"wp:attachment":[{"href":"https:\/\/lbajiele.com\/es\/wp-json\/wp\/v2\/media?parent=2722"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/lbajiele.com\/es\/wp-json\/wp\/v2\/categories?post=2722"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/lbajiele.com\/es\/wp-json\/wp\/v2\/tags?post=2722"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}