{"id":2722,"date":"2026-08-22T14:27:00","date_gmt":"2026-08-22T14:27:00","guid":{"rendered":"https:\/\/lbajiele.com\/?p=2722"},"modified":"2026-10-23T00:44:33","modified_gmt":"2026-10-23T00:44:33","slug":"75-kva-transformer-amps-guide","status":"publish","type":"post","link":"https:\/\/lbajiele.com\/fr\/blog\/75-kva-transformer-amps-guide\/","title":{"rendered":"Guide des amp\u00e9rages d'un transformateur de 75 kVA : courant primaire et secondaire"},"content":{"rendered":"<p><strong>Un transformateur de 75 kVA n'a pas une seule valeur nominale d'amp\u00e9rage fixe.<\/strong> Current depends on phase and voltage: single-phase current is 75,000 \u00f7 V; three-phase line current is 75,000 \u00f7 (1.732 \u00d7 V). For example, 75 kVA is about 90.2 A at 480 V three-phase and 208.2 A at 208 V three-phase.<\/p>\n<div class=\"lbaji-key-takeaways\">\n<h2>Points cl\u00e9s<\/h2>\n<ul>\n<li>At 75 kVA, full-load amps depend on phase and the voltage at the side being measured.<\/li>\n<li>At 480 V three phase the result is 90.2 A; at 208 V three phase it is 208.2 A.<\/li>\n<li>These are winding current calculations, not automatic breaker, cable, or safe continuous-load ratings.<\/li>\n<\/ul>\n<\/div>\n<h2>Formule de courant pour 75 kVA<\/h2>\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" alt=\"Three-phase transformer and switchboard used for full-load current calculations\" loading=\"lazy\" src=\"https:\/\/lbajiele.com\/wp-content\/uploads\/2026\/08\/three-phase-kva-to-amps.png\"\/><figcaption>Transformateur triphas\u00e9 et tableau \u00e9lectrique utilis\u00e9s pour les calculs de courant \u00e0 pleine charge.<\/figcaption><\/figure>\n<p>Pour le monophas\u00e9, I = kVA \u00d7 1 000 \u00f7 V. Pour le triphas\u00e9, I = kVA \u00d7 1 000 \u00f7 (\u221a3 \u00d7 tension entre phases). Utilisez la tension de la plaque signal\u00e9tique plut\u00f4t qu'une hypoth\u00e8se nominale. Ces \u00e9quations d\u00e9crivent le courant apparent \u00e0 pleine charge ; le dimensionnement des conducteurs et des dispositifs de protection suit toujours le code applicable, le r\u00e9gime de charge, la temp\u00e9rature et la m\u00e9thode d'installation.<\/p>\n<section class=\"lbaji-article-table\">\n<h2>Tableau de comparaison rapide et de s\u00e9lection<\/h2>\n<p>Utilisez ce tableau comme un r\u00e9capitulatif rapide des principales d\u00e9cisions d'ing\u00e9nierie et d'approvisionnement expliqu\u00e9es dans l'article.<\/p>\n<figure class=\"wp-block-table is-style-stripes\" style=\"overflow-x:auto;max-width:100%\">\n<table>\n<thead>\n<tr>\n<th scope=\"col\">Zone de d\u00e9cision<\/th>\n<th scope=\"col\">Sens pratique<\/th>\n<th scope=\"col\">Que v\u00e9rifier<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Formule de courant pour 75 kVA<\/td>\n<td>Pour le monophas\u00e9, I = kVA \u00d7 1 000 \u00f7 V.<\/td>\n<td>Pour le triphas\u00e9, I = kVA \u00d7 1 000 \u00f7 (\u221a3 \u00d7 tension entre phases).<\/td>\n<\/tr>\n<tr>\n<td>Courants \u00e0 pleine charge usuels pour 75 kVA<\/td>\n<td>\u00c0 240 V monophas\u00e9, le courant calcul\u00e9 est de 312,5 A, et \u00e0 480 V monophas\u00e9, il est de 156,3 A.<\/td>\n<td>For three phase, common results are 90.2 A at 480 V, 104.3 A at 415 V, 108.3 A at 400 V, 208.2 A at 208 V and 180.4 A at 240 V.<\/td>\n<\/tr>\n<tr>\n<td>Amplificateurs principaux et secondaires<\/td>\n<td>Un transformateur triphas\u00e9 de 480 \u00e0 208Y\/120 V de 75 kVA d\u00e9bite environ 90 A du c\u00f4t\u00e9 480 V et 208 A du c\u00f4t\u00e9 208 V.<\/td>\n<td>Le transformateur modifie la relation tension-courant tandis que la puissance apparente reste approximativement constante, hors pertes.<\/td>\n<\/tr>\n<tr>\n<td>Dimensionnement des disjoncteurs et des conducteurs<\/td>\n<td>Ne choisissez pas de disjoncteurs en vous basant uniquement sur l'intensit\u00e9 \u00e0 pleine charge.<\/td>\n<td>Les codes autorisent ou exigent des dispositions de protection sp\u00e9cifiques, soit uniquement primaires, soit primaires et secondaires, et tiennent compte des courants d'appel.<\/td>\n<\/tr>\n<tr>\n<td>Est-ce que 75 kVA est suffisant ?<\/td>\n<td>Additionnez les kVA de charge plut\u00f4t que de simplement additionner les amp\u00e8res \u00e0 diff\u00e9rentes tensions.<\/td>\n<td>Consid\u00e9rez la demande, le d\u00e9marrage du moteur, les harmoniques non lin\u00e9aires, l'extension future, la temp\u00e9rature ambiante et la r\u00e9gulation de tension acceptable.<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/figure>\n<\/section>\n<h2>Courants \u00e0 pleine charge usuels pour 75 kVA<\/h2>\n<p>At 240 V single phase the calculated current is 312.5 A, and at 480 V single phase it is 156.3 A. For three phase, common results are 90.2 A at 480 V, 104.3 A at 415 V, 108.3 A at 400 V, 208.2 A at 208 V and 180.4 A at 240 V. Rounding should not be used to conceal a voltage mismatch.<\/p>\n<h2>Amplificateurs principaux et secondaires<\/h2>\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" alt=\"Coordinated transformer primary and secondary protection\" loading=\"lazy\" src=\"https:\/\/lbajiele.com\/wp-content\/uploads\/2026\/08\/transformer-breaker-fuse-sizing.png\"\/><figcaption>Protection coordonn\u00e9e du primaire et du secondaire d'un transformateur.<\/figcaption><\/figure>\n<p>Un transformateur triphas\u00e9 de 480 \u00e0 208Y\/120 V transporte environ 90 A du c\u00f4t\u00e9 480 V et 208 A du c\u00f4t\u00e9 208 V \u00e0 75 kVA. Le transformateur modifie la relation tension-courant tandis que la puissance apparente reste approximativement constante, hors pertes. Les conducteurs primaires et secondaires n\u00e9cessitent donc des ampacit\u00e9s et des protections diff\u00e9rentes.<\/p>\n<h2>Dimensionnement des disjoncteurs et des conducteurs<\/h2>\n<p>Ne choisissez pas les disjoncteurs en vous basant uniquement sur le courant \u00e0 pleine charge. Les codes autorisent ou exigent des dispositions de protection sp\u00e9cifiques (c\u00f4t\u00e9 primaire seul ou primaire et secondaire) et tiennent compte du courant d'appel. Les conducteurs doivent \u00eatre v\u00e9rifi\u00e9s pour la charge continue, la temp\u00e9rature d'isolement, les caract\u00e9ristiques nominales des bornes, la correction de temp\u00e9rature ambiante, le regroupement et la chute de tension. Un conception qualifi\u00e9 doit coordonner les dispositifs amont et aval.<\/p>\n<h2>Est-ce que 75 kVA est suffisant ?<\/h2>\n<p>Additionnez les kVA de charge plut\u00f4t que de vous contenter d'additionner les amp\u00e8res sous diff\u00e9rentes tensions. Prenez en compte la demande, le d\u00e9marrage des moteurs, les harmoniques non lin\u00e9aires, l'expansion future, la temp\u00e9rature ambiante et la r\u00e9gulation de tension acceptable. Un appareil qui convient \u00e0 une charge stable peut provoquer une chute de tension excessive lors de l'acc\u00e9l\u00e9ration d'un moteur ou surchauffer avec un courant riche en harmoniques.<\/p>\n<h2>V\u00e9rifications de la plaque signal\u00e9tique et des approvisionnements<\/h2>\n<p>Confirmez la tension primaire et secondaire, la phase, la fr\u00e9quence, le groupe de couplage ou la connexion des enroulements, les prises, l'imp\u00e9dance, la classe d'isolation, l'\u00e9l\u00e9vation de temp\u00e9rature, l'enveloppe, le rendement, le niveau sonore et les accessoires. Pour les remplacements, v\u00e9rifiez l'encombrement au sol, l'entr\u00e9e des c\u00e2bles, la disposition des bornes, le courant de d\u00e9faut disponible et la protection en amont avant de commander.<\/p>\n<section class=\"lbaji-gsc-update\">\n<h2>75 kVA Full-Load Amps by Voltage and Phase<\/h2>\n<p>The table below uses a 75,000 VA nameplate rating. For three-phase rows, voltage means line-to-line voltage and current means line current. Single-phase rows use the voltage across the winding. Values are rounded to one decimal ampere; the design calculation should use the actual nameplate voltage and the project electrical drawings.<\/p>\n<figure class=\"wp-block-table is-style-stripes\" style=\"overflow-x:auto;max-width:100%\">\n<table>\n<thead>\n<tr>\n<th scope=\"col\">System voltage<\/th>\n<th scope=\"col\">Single-phase full-load current<\/th>\n<th scope=\"col\">Three-phase full-load line current<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>208 V<\/td>\n<td>360.6 A<\/td>\n<td>208.2 A<\/td>\n<\/tr>\n<tr>\n<td>230 V<\/td>\n<td>326.1 A<\/td>\n<td>188.3 A<\/td>\n<\/tr>\n<tr>\n<td>240 V<\/td>\n<td>312,5 A<\/td>\n<td>180,4 A<\/td>\n<\/tr>\n<tr>\n<td>400 V<\/td>\n<td>187,5 A<\/td>\n<td>108,3 A<\/td>\n<\/tr>\n<tr>\n<td>415 V<\/td>\n<td>180.7 A<\/td>\n<td>104.3 A<\/td>\n<\/tr>\n<tr>\n<td>480 V<\/td>\n<td>156.3 A<\/td>\n<td>90.2 A<\/td>\n<\/tr>\n<tr>\n<td>600 V<\/td>\n<td>125,0 A<\/td>\n<td>72.2 A<\/td>\n<\/tr>\n<\/tbody>\n<\/table><figcaption>Calculated from I = 75,000\/V for single phase and I = 75,000\/(\u221a3 \u00d7 V) for balanced three phase. Formula basis: <a href=\"https:\/\/www.se.com\/us\/en\/faqs\/FA101694\/\" target=\"_blank\" rel=\"noopener nofollow\">Schneider Electric transformer capacity FAQ<\/a> et le <a href=\"https:\/\/www.electrical-installation.org\/enwiki\/Choice_of_transformer_rating\" target=\"_blank\" rel=\"noopener nofollow\">Electrical Installation Guide<\/a>.<\/figcaption><\/figure>\n<p>This table is a current lookup, not a promise that every 75 kVA transformer is available in every listed voltage or connection. Confirm the actual primary and secondary nameplate ratings, winding connection, frequency, taps and cooling designation. Never use a 400 V row for a 480 V winding simply because both are described as industrial three-phase systems.<\/p>\n<h2>Worked Example: 480 V Primary to 208Y\/120 V Secondary<\/h2>\n<p>Consider a balanced 75 kVA, three-phase step-down transformer with a 480 V line-to-line primary and a 208Y\/120 V secondary. On the primary, the theoretical full-load line current is 75,000 \u00f7 (\u221a3 \u00d7 480) = 90.2 A. On the secondary, it is 75,000 \u00f7 (\u221a3 \u00d7 208) = 208.2 A. The 120 V marking identifies line-to-neutral voltage on the wye secondary. For the three-phase calculation, use 208 V line-to-line, not 120 V.<\/p>\n<p>The higher secondary current is expected: voltage falls while apparent power remains approximately the same, allowing for real transformer losses. When reviewing a one-line diagram, calculate each side separately. Check the transformer nameplate before ordering a breaker or cable; current alone does not establish conductor ampacity, breaker setting or short-circuit duty.<\/p>\n<h2>How Many kW Can a 75 kVA Transformer Supply?<\/h2>\n<p>kVA measures apparent power; kW measures real power. For a balanced load, estimated real power is kW = 75 \u00d7 power factor. At 0.8 power factor, that is 60 kW. At 0.9 power factor, it is 67.5 kW. At unity power factor, the mathematical maximum is 75 kW. These figures do not replace a load study: harmonics, motor starting, duty cycle, ambient temperature and the transformer&#8217;s actual thermal rating still matter.<\/p>\n<p>Do not apply an automatic \u201c80% of 75 kVA\u201d rule to every transformer. A continuous-load rule for a particular protective device or installation is not the same as the transformer&#8217;s nameplate thermal capacity. Ask the electrical designer to document the applicable code, manufacturer instructions, load profile and required spare capacity.<\/p>\n<h2>When 75 kVA Is Too Small<\/h2>\n<p>Compare the highest expected coincident demand in kVA with the transformer&#8217;s rating under the actual operating conditions. If several loads start at different times, a simple sum of every nameplate rating may overstate demand. If large motors start together, steady-state current can understate the short-duration voltage dip. Record both cases rather than treating a single amperage number as the entire sizing decision.<\/p>\n<p>For example, a balanced 480 V three-phase load drawing 100 A represents approximately \u221a3 \u00d7 480 \u00d7 100 \u00f7 1,000 = 83.1 kVA before any allowance for expansion. That exceeds 75 kVA. Conversely, a 60 A load at the same voltage represents about 49.9 kVA, leaving apparent-power headroom, subject to starting current, thermal conditions and other connected loads. Schneider Electric&#8217;s <a href=\"https:\/\/www.se.com\/us\/en\/faqs\/FA101694\/\" target=\"_blank\" rel=\"noopener nofollow\">capacity guidance<\/a> explicitly notes that motor and specialty loads may require more than the simple arithmetic result.<\/p>\n<h2>What to Send With a 75 kVA Transformer Inquiry<\/h2>\n<p>Give the supplier the primary and secondary voltage, phase, frequency, connection, installation site, required enclosure, ambient conditions and available fault current. Include the load schedule, motor-starting information, harmonic-producing equipment and space limits. Ask for a data sheet showing nameplate ratings, impedance, losses, temperature rise, dimensions and routine test documents. If replacing a unit, provide photos of the existing nameplate and terminal layout, not only the phrase \u201c75 kVA transformer.\u201d<\/p>\n<p>For adjacent calculations, use our <a href=\"https:\/\/lbajiele.com\/fr\/blog\/how-much-load-can-a-63-kva-transformer-handle\/\">63 kVA load-capacity example<\/a>, <a href=\"https:\/\/lbajiele.com\/fr\/blog\/amps-convert-to-kva-calculator-and-formula-guide\/\">amps-to-kVA formula guide<\/a> et <a href=\"https:\/\/lbajiele.com\/fr\/blog\/guide-des-fusibles-de-transformateur\/\">guide des fusibles de transformateur<\/a>. Review the <a href=\"https:\/\/lbajiele.com\/fr\/categorie-produit\/transformer\/\">gamme de produits de transformateurs<\/a> for available configurations; confirm project-specific values with the manufacturer.<\/p>\n<h2>Three-Phase Transformer Video Lesson<\/h2>\n<p>For the relationship between phase voltage, line voltage and transformer connections, this NPTEL university lecture provides a useful technical introduction. The calculation table above remains the direct answer for 75 kVA current.<\/p>\n<div class=\"lbaji-video\" style=\"position:relative;padding-bottom:56.25%;height:0;overflow:hidden\"><iframe src=\"https:\/\/www.youtube-nocookie.com\/embed\/s86tXyDQIxg\" title=\"NPTEL Introduction to Three Phase Transformer\" loading=\"lazy\" allow=\"accelerometer; encrypted-media; gyroscope; picture-in-picture\" allowfullscreen style=\"position:absolute;top:0;left:0;width:100%;height:100%;border:0\"><\/iframe><\/div>\n<p><a href=\"https:\/\/www.youtube.com\/watch?v=s86tXyDQIxg\" target=\"_blank\" rel=\"noopener nofollow\">Watch NPTEL&#8217;s Introduction to Three Phase Transformer on YouTube<\/a>.<\/p>\n<\/section>\n<h2>\u00c9quipement LBAJI associ\u00e9<\/h2>\n<p>Examinez les \u00e9l\u00e9ments pertinents <a href=\"https:\/\/lbajiele.com\/fr\/categorie-produit\/transformer\/\">Gamme de produits LBAJI<\/a> et le soutien <a href=\"https:\/\/lbajiele.com\/fr\/blog\/complete-guide-to-transformer-capacity-size-dimensions\/\">Guide des piliers sur la capacit\u00e9, la taille et les dimensions des transformateurs<\/a>. Veuillez envoyer le sch\u00e9ma unifilaire, les caract\u00e9ristiques nominales, la quantit\u00e9 et l'environnement pour une configuration sp\u00e9cifique au projet.<\/p>\n<section class=\"lbaji-visible-faq\" aria-label=\"Foire aux questions\">\n<h2>Foire aux questions<\/h2>\n<div class=\"rank-math-list-item\" id=\"faq-question-1\">\n<h3 class=\"rank-math-question\">How many amps is a 75 kVA transformer at 480 V three phase?<\/h3>\n<div class=\"rank-math-answer\">\n<p>Approximately 90.2 A at full load, calculated as 75,000 divided by 1.732 times 480.<\/p>\n<\/div>\n<\/div>\n<div class=\"rank-math-list-item\" id=\"faq-question-2\">\n<h3 class=\"rank-math-question\">How many amps is 75 kVA at 208 V three phase?<\/h3>\n<div class=\"rank-math-answer\">\n<p>Approximately 208.2 A at full load.<\/p>\n<\/div>\n<\/div>\n<div class=\"rank-math-list-item\" id=\"faq-question-3\">\n<h3 class=\"rank-math-question\">Is kVA the same as kW?<\/h3>\n<div class=\"rank-math-answer\">\n<p>No. kVA is apparent power; kW is real power and equals kVA multiplied by power factor for a balanced load.<\/p>\n<\/div>\n<\/div>\n<div class=\"rank-math-list-item\" id=\"faq-question-4\">\n<h3 class=\"rank-math-question\">Can I size the breaker exactly at full-load current?<\/h3>\n<div class=\"rank-math-answer\">\n<p>Not automatically. Transformer inrush and electrical-code protection rules must be applied.<\/p>\n<\/div>\n<\/div>\n<div class=\"rank-math-list-item\" id=\"faq-question-5\">\n<h3 class=\"rank-math-question\">Why are secondary amps higher than primary amps?<\/h3>\n<div class=\"rank-math-answer\">\n<p>A step-down transformer reduces voltage, so current rises for approximately the same apparent power.<\/p>\n<\/div>\n<\/div>\n<\/section>\n<section class=\"lbaji-decision-aid\">\n<h2>Flux de travail d'\u00e9valuation pratique<\/h2>\n<p>Pour les amp\u00e8res d'un transformateur de 75 kva, utilisez un flux de travail document\u00e9 plut\u00f4t qu'un choix bas\u00e9 uniquement sur le catalogue. Tout d'abord, gelez les entr\u00e9es du syst\u00e8me et les limites de fonctionnement. Ensuite, comparez les options de construction ou de service disponibles par rapport \u00e0 l'environnement r\u00e9el. Puis, v\u00e9rifiez les calculs, les interfaces de protection et les tests de r\u00e9ception. Enfin, enregistrez les d\u00e9rogations approuv\u00e9es et conservez les r\u00e9sultats de r\u00e9f\u00e9rence pour la mise en service et la maintenance.<\/p>\n<ol>\n<li>Examinez les courants \u00e0 pleine charge courants pour 75 kva et consignez la d\u00e9cision sp\u00e9cifique au projet.<\/li>\n<li>Examiner les amplificateurs primaires et secondaires et enregistrer la d\u00e9cision sp\u00e9cifique au projet.<\/li>\n<li>V\u00e9rifier le dimensionnement des disjoncteurs et des conducteurs et consigner la d\u00e9cision sp\u00e9cifique au projet.<\/li>\n<li>V\u00e9rifier si un transformateur de 75 kva est suffisant et enregistrer la d\u00e9cision sp\u00e9cifique au projet.<\/li>\n<\/ol>\n<\/section>\n<section class=\"lbaji-acceptance-records\">\n<h2>Dossiers d'acceptation \u00e0 conserver<\/h2>\n<p>Conserver la fiche technique approuv\u00e9e, les plans, la liste des d\u00e9rogations, les certificats de mat\u00e9riaux le cas \u00e9ch\u00e9ant, les rapports d'essais de routine et sp\u00e9ciaux, les r\u00e9glages de protection, les r\u00e9sultats de mise en service, les photographies et les d\u00e9tails de la plaque signal\u00e9tique finale. Enregistrer les conditions d'essai ainsi que les valeurs, car la temp\u00e9rature, la m\u00e9thode instrumentale et le raccordement peuvent affecter la comparaison. Ces documents \u00e9tablissent la r\u00e9f\u00e9rence utilis\u00e9e pour analyser ult\u00e9rieurement les alarmes, les changements de charge ou la d\u00e9t\u00e9rioration. Ils \u00e9vitent \u00e9galement que des \u00e9quipements de remplacement ne soient command\u00e9s \u00e0 partir d'une description incompl\u00e8te apr\u00e8s un changement de personnel ou de fournisseurs.<\/p>\n<\/section>\n<section class=\"lbaji-technical-references\">\n<h2>R\u00e9f\u00e9rences techniques et lectures compl\u00e9mentaires<\/h2>\n<ul>\n<li><a href=\"https:\/\/www.energy.gov\/cmei\/buildings\/distribution-transformers\" rel=\"noopener noreferrer nofollow\" target=\"_blank\">Ressources du D\u00e9partement de l'\u00c9nergie des \u00c9tats-Unis (DOE) concernant les transformateurs de distribution<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/588\" rel=\"noopener noreferrer nofollow\" target=\"_blank\">transformateurs de puissance CEI 60076-1<\/a><\/li>\n<li><a href=\"https:\/\/www.nfpa.org\/codes-and-standards\" rel=\"noopener noreferrer nofollow\" target=\"_blank\">Codes et normes \u00e9lectriques de la NFPA<\/a><\/li>\n<\/ul>\n<\/section>\n<h2>Conclusion<\/h2>\n<p>A 75 kVA transformer does not have one fixed amp rating. Current depends on phase and voltage: single-phase current is 75,000 \u00f7 V; three-phase line current is 75,000 \u00f7 (1.732 \u00d7 V). For example, 75 kVA is about 90.2 A at 480 V three-phase and 208.2 A at 208 V three-phase. Use project data and documented acceptance criteria before purchase, installation or service.<\/p>","protected":false},"excerpt":{"rendered":"<p>75 kVA transformer amps depend on voltage and phase. See single- and three-phase current charts, a 480-to-208 V example, and sizing checks.<\/p>","protected":false},"author":6,"featured_media":2721,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[52],"tags":[85,66,65],"class_list":["post-2722","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-transformers","tag-kva-calculations","tag-transformer-capacity","tag-transformer-sizing"],"blocksy_meta":[],"acf":[],"_links":{"self":[{"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/posts\/2722","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/users\/6"}],"replies":[{"embeddable":true,"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/comments?post=2722"}],"version-history":[{"count":6,"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/posts\/2722\/revisions"}],"predecessor-version":[{"id":4831,"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/posts\/2722\/revisions\/4831"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/media\/2721"}],"wp:attachment":[{"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/media?parent=2722"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/categories?post=2722"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/tags?post=2722"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}