{"id":3843,"date":"2026-10-02T07:00:00","date_gmt":"2026-10-02T07:00:00","guid":{"rendered":"https:\/\/lbajiele.com\/?p=3843"},"modified":"2026-10-04T12:20:18","modified_gmt":"2026-10-04T12:20:18","slug":"how-to-test-power-factor","status":"publish","type":"post","link":"https:\/\/lbajiele.com\/fr\/blog\/how-to-test-power-factor\/","title":{"rendered":"How To Test Power Factor?"},"content":{"rendered":"<p><strong>To test power factor, measure real electrical input power and apparent input power at the same circuit boundary with a correctly configured power analyzer.<\/strong> Power factor is P\/S; motor efficiency is mechanical output power divided by real electrical input power. These are different quantities. Record the operating load, analyzer configuration, voltage\/current channel mapping and the instrument&#8217;s sign convention. Confirm whether the result is true power factor or displacement power factor before comparing readings. An ordinary current-only clamp measurement cannot establish power factor.<\/p><figure class=\"wp-block-image\"><img decoding=\"async\" alt=\"GGD Low-Voltage Switchgear shown as a product enclosure reference\" loading=\"lazy\" src=\"https:\/\/lbajiele.com\/wp-content\/uploads\/2026\/04\/GGD-Low-voltage-switchgear.webp\"\/><figcaption>GGD Low-Voltage Switchgear reference image. Exterior appearance does not establish internal components, protection settings or project ratings.<\/figcaption><\/figure>\n<h2>Qu'est-ce que le terme \u00ab leading \u00bb et \u00ab lagging \u00bb signifie ?<\/h2>\n<p>Dans un circuit sinuso\u00efdal, la tension est retard\u00e9e par le courant lorsque la charge inductive stocke de l'\u00e9nergie dans un champ magn\u00e9tique. Le courant suit la tension lorsque la charge capacitive stocke de l'\u00e9nergie dans un champ \u00e9lectrique. La puissance r\u00e9elle est mesur\u00e9e en kW, la puissance r\u00e9active en kvar et la puissance apparente en kVA. La relation est : facteur de puissance = kW\/kVA, tandis que le signe de kvar ou l'angle de phase indique la direction.<\/p>\n<div aria-label=\"Scrollable comparison table\" class=\"lbaji-table-scroll\" role=\"region\" style=\"width:100%;max-width:100%;overflow-x:auto;-webkit-overflow-scrolling:touch;\" tabindex=\"0\"><table style=\"min-width:620px;width:100%;border-collapse:collapse;\"><thead><tr><th>Observation<\/th><th>Probable condition<\/th><th>V\u00e9rifier<\/th><\/tr><\/thead><tbody><tr><td>Positive ou importation de kvar sur une charge inductive<\/td><td>Facteur de puissance d\u00e9croissant<\/td><td>Convention de mesure et signe de phase<\/td><\/tr><tr><td>D\u00e9faillance ou exportation de kvar avec des condensateurs connect\u00e9s<\/td><td>Facteur de puissance \u00e9lev\u00e9<\/td><td>\u00c9tat du condensateur et polarit\u00e9 du CT<\/td><\/tr><tr><td>PF proche de 1 mais kvar change de signe<\/td><td>Transition entre la direction et le retard<\/td><td>S\u00e9quence de commutation du chargeur et du condensateur<\/td><\/tr><tr><td>Le signe PF semble incoh\u00e9rent<\/td><td>Possible erreur de polarit\u00e9 ou de phase de la cartographie CT\/PT<\/td><td>Sch\u00e9ma \u00e9lectrique et test de phase<\/td><\/tr><tr><td>Haute PF pendant le d\u00e9marrage du moteur<\/td><td>Haute intensit\u00e9 de la conduction \u00e9lectrique et de la d\u00e9charge transitoire<\/td><td>M\u00e9thode de d\u00e9marrage et enregistrement d\u2019\u00e9v\u00e9nements<\/td><\/tr><\/tbody><\/table><\/div>\n<h2>Utilisez le signe de puissance r\u00e9active du compteur<\/h2><p>Check sensor direction before interpreting a negative reading. <a href=\"https:\/\/www.fluke.com\/en-us\/learn\/blog\/power-quality\/arrow-on-current-clamp\" rel=\"noopener nofollow\" target=\"_blank\">Fluke\u2019s current-clamp direction guidance<\/a> explains why reversing the sensor changes measured power direction. A sign error must be resolved before deciding whether power is actually being exported.<\/p>\n<p>De nombreux appareils de mesure de la qualit\u00e9 de l'\u00e9nergie affichent kW, kvar, kVA, PF et une indication de retard\/avance. Lisez le manuel de l'appareil car les conventions de notation diff\u00e8rent. Certains affichent un kvar positif pour la charge \u00e0 retard et un kvar n\u00e9gatif pour la charge \u00e0 avance ; d'autres utilisent un langage d'importation\/exportation. Ne copiez pas une r\u00e8gle de notation d'un autre appareil sans v\u00e9rifier sa s\u00e9quence de phases et l'orientation de la tension de contact.<\/p>\n<p>Notez l\u2019affichage pendant que la charge inductive connue est en fonctionnement, puis connectez ou d\u00e9connectez une phase de condensateur v\u00e9rifi\u00e9e et observez les changements. Si kvar tend vers z\u00e9ro, le condensateur corrige la charge inductive. Si elle d\u00e9passe z\u00e9ro et devient capacitive, le syst\u00e8me devient conducteur \u00e0 ce point de fonctionnement. Une conductivit\u00e9 excessive peut entra\u00eener des probl\u00e8mes de surtension ou de r\u00e9sonance.<\/p>\n<h2>Calculer \u00e0 partir de kW et kvar<\/h2>\n<p>For a suitable sinusoidal single-phase or balanced three-phase model, apparent power magnitude is S = \u221a(P\u00b2 + Q\u00b2), and power-factor magnitude is |PF| = |P|\/S. For distorted or unbalanced systems, use the analyzer\u2019s defined apparent-power method; signed kW and kvar alone do not necessarily determine true apparent power. The phase angle can be calculated as \u03c6 = atan2(Q, P), with the sign of Q indicating the chosen leading or lagging convention. Keep the signed values and the convention in the report instead of recording only the absolute PF.<\/p>\n<p>Par exemple, une charge de 80 kW et +60 kvar a une capacit\u00e9 de 100 kVA et un PF de 0,80 selon une convention o\u00f9 un kvar positif signifie retard. Si la correction du condensateur modifie la valeur \u00e0 80 kW et -20 kvar, la valeur est d\u2019environ 82,5 kVA et le PF est d\u2019environ 0,97. Le changement de signe est le r\u00e9sultat important ; l\u2019interpr\u00e9tation exacte suit toujours la convention du compteur.<\/p>\n<h2>Contr\u00f4lez la forme d'onde et l'angle de phase actuels<\/h2>\n<p>Un analyseur de puissance peut afficher les formes d\u2019onde de tension et de courant et calculer l\u2019angle de phase pour chaque phase. Une forme d\u2019onde de courant retard\u00e9e atteint son maximum apr\u00e8s la r\u00e9f\u00e9rence de tension ; une forme d\u2019onde avance atteint son maximum avant la r\u00e9f\u00e9rence. Les harmoniques compl\u00e8tent ainsi une vue simple \u00e0 angle fixe ; il est donc n\u00e9cessaire de v\u00e9rifier s\u00e9par\u00e9ment le facteur de puissance harmonique et le facteur de puissance r\u00e9el lorsque des charges non lin\u00e9aires sont pr\u00e9sentes.<\/p>\n<p>v\u00e9rifier la s\u00e9quence des phases, la polarit\u00e9 du CT, la polarit\u00e9 du PT et la cartographie des canaux. Une CT invers\u00e9e peut faire para\u00eetre une charge inductive capacitive ou cr\u00e9er une valeur kW n\u00e9gative. Comparez le r\u00e9sultat de l\u2019analyseur \u00e0 une charge de r\u00e9f\u00e9rence connue et au sch\u00e9ma \u00e0 une ligne. N\u2019ajustez jamais une batterie de condensateurs en fonction d\u2019un signe qui n\u2019a pas \u00e9t\u00e9 valid\u00e9.<\/p>\n<figure><img decoding=\"async\" alt=\"SG(B)  Environment-Friendly Dry-Type Transformer shown as a product enclosure reference\" loading=\"lazy\" src=\"https:\/\/lbajiele.com\/wp-content\/uploads\/2026\/04\/ENVIRONMENT-FRIENDLYDRY-TYPE-TRANSFORMER.webp\"\/><figcaption>SG(B)  Environment-Friendly Dry-Type Transformer reference image. Exterior appearance does not establish internal components, protection settings or project ratings.<\/figcaption><\/figure>\n<h2>Comportement du moteur et du transformateur<\/h2>\n<p>Les moteurs \u00e0 induction fonctionnent normalement avec un facteur de puissance de d\u00e9viation retard\u00e9, surtout \u00e0 faible charge et lors de la mise en marche. Les transformateurs consomment \u00e9galement une puissance r\u00e9active de magn\u00e9tisation. Le facteur de puissance varie en fonction de la charge, de la tension et du mode de commande. Un moteur qui semble acceptable \u00e0 pleine charge peut \u00eatre fortement retard\u00e9 lorsque la charge est faible. Notez le courant de fonctionnement, en kW, en kvar, en tension et en vitesse ensemble.<\/p>\n<p>Les variateurs de fr\u00e9quence peuvent am\u00e9liorer le facteur de puissance de d\u00e9placement de l\u2019entr\u00e9e tout en produisant encore des harmoniques de courant. Un groupe de condensateurs connect\u00e9 directement \u00e0 la sortie du variateur n\u2019est g\u00e9n\u00e9ralement pas appropri\u00e9. Avant d\u2019ajouter du mat\u00e9riel de correction, veuillez consulter le manuel du variateur, l\u2019\u00e9tude des harmoniques et les exigences de d\u00e9tuning. LBAJI <a href=\"https:\/\/lbajiele.com\/fr\/produit\/ggd-low-voltage-switchgear\/\">Tableau basse tension GGD<\/a> La page est une r\u00e9f\u00e9rence de produit destin\u00e9e \u00e0 la distribution ; le syst\u00e8me de filtration doit \u00eatre s\u00e9lectionn\u00e9 en fonction de l\u2019\u00e9tude de conception du syst\u00e8me.<\/p>\n<h2>Les groupes de condensateurs et la surcorrection<\/h2>\n<p>Les groupes de condensateurs automatiques passent en phase avec le courant de charge. Si les phases restent connect\u00e9es pendant que les moteurs sont arr\u00eat\u00e9s, le syst\u00e8me peut devenir d\u00e9faillant. Le d\u00e9faillissement peut augmenter la tension, interagir avec les transformateurs et provoquer une r\u00e9sonance avec l\u2019inductance du r\u00e9seau. Utilisez un contr\u00f4leur avec la position correcte des CT, la valeur PF cible, un d\u00e9lai de commutation et une dur\u00e9e de d\u00e9charge. V\u00e9rifiez que chaque phase dispose de fusibles, de contacteurs et de r\u00e9acteurs, selon les besoins, ainsi que de r\u00e9sistances de d\u00e9charge s\u00fbres.<\/p>\n<p>Mesurer la PF au point sp\u00e9cifi\u00e9 par les exigences de l\u2019entreprise d\u2019\u00e9lectricit\u00e9 ou du projet. Un tableau local peut afficher une valeur proche de l\u2019unit\u00e9 alors que le flux principal reste faible car un autre alimentateur n\u2019est pas compens\u00e9. Une batterie de condensateurs peut \u00e9galement corriger un alimentateur tout en provoquant une surcompensation la nuit ou lors de faibles niveaux de production. Les lectures de tendance sur l\u2019ensemble du cycle de fonctionnement.<\/p>\n<h2>Mesure en trois phases<\/h2>\n<p>Pour un syst\u00e8me triphas\u00e9 \u00e9quilibr\u00e9, utilisez la m\u00e9thode triphas\u00e9e de l\u2019analyseur et ajustez correctement les valeurs de tension entre phase et phase ou entre phase et neutre. Dans un syst\u00e8me non \u00e9quilibr\u00e9, v\u00e9rifiez les kW, kvar, courant et PF de chaque phase. Un seul PF total peut masquer une phase positive et une phase n\u00e9gative. V\u00e9rifiez \u00e9galement la tension neutre, la s\u00e9quence des phases et le rapport entre le transformateur de phase.<\/p>\n<p>L\u2019installation de CT est importante lorsque les charges comprennent des groupes \u00e9lectrog\u00e8nes, des convertisseurs photovolta\u00efques, des interrupteurs de transfert ou plusieurs appareils \u00e0 courant alternatif. Le CT doit pouvoir d\u00e9tecter le courant qui doit \u00eatre r\u00e9gul\u00e9 par le contr\u00f4leur. Un signe qui change lorsque le commutateur de transfert est en marche peut indiquer que le CT est sur le mauvais c\u00f4t\u00e9 du commutateur. Tracez le trajet du courant sur la ligne unique.<\/p>\n<h2>Commencement de fonctionnement et d\u00e9pannage<\/h2>\n<p>Commencez par une charge connue et v\u00e9rifiez la cartographie des phases du compteur. Notez kW, kvar, kVA, PF, tension, courant, fr\u00e9quence et harmoniques. \u00c9teignez un \u00e9tage de condensateur ou une charge inductive connue \u00e0 la fois et v\u00e9rifiez le changement de signe attendu. Si la lecture n\u2019est pas plausible, v\u00e9rifiez la polarit\u00e9 du CT, le c\u00e2blage du PT, la s\u00e9quence de phase, l\u2019\u00e9chelle, le raccordement \u00e0 la masse et la configuration du firmware avant de changer le mat\u00e9riel.<\/p>\n<p>Lorsqu\u2019un contr\u00f4leur PF effectue des recherches entre les phases, v\u00e9rifiez le d\u00e9lai de r\u00e9examen, la zone morte, le temps de d\u00e9charge, la localisation de la CT et la charge minimale. Lorsque le PF se comporte de mani\u00e8re inattendue, inspectez les contacteurs bloqu\u00e9s, les phases soud\u00e9es, le transformateur faiblement charg\u00e9 et les r\u00e9glages de puissance r\u00e9active de l\u2019onduleur. N\u2019\u00e9teignez pas la protection ni ne contournez un contr\u00f4leur sans proc\u00e9dure approuv\u00e9e.<\/p>\n<h2>Rapports<\/h2>\n<p>Un rapport utile indique le mod\u00e8le d\u2019instrument, la calibration, la configuration du c\u00e2blage, la convention d\u2019affichage, la p\u00e9riode d\u2019\u00e9chantillonnage, la charge de fonctionnement, les \u00e9tages du condensateur, le kW, le kvar, le kVA, le PF et les valeurs harmoniques. Incluez des captures d\u2019\u00e9cran ou des enregistrements d\u2019\u00e9v\u00e9nements lorsque le sens de la direction change. <a href=\"https:\/\/lbajiele.com\/fr\/blog\/leading-vs-lagigng-current-power-factor-comparison-guide\/\">Comparaison entre les leaders et les derniers<\/a> offre une r\u00e9f\u00e9rence de terminologie de base ; le rapport de projet doit conserver les signaux mesur\u00e9s et les hypoth\u00e8ses.<\/p>\n<p>Pour les installations utilisant des sources d\u2019\u00e9nergie renouvelable, il convient de distinguer le contr\u00f4le de la puissance r\u00e9active par l\u2019onduleur de la correction par condensateur. <a href=\"https:\/\/lbajiele.com\/fr\/produit\/bwg-800-photovoltaic-grid-connected-cabinet\/\">Armoire BWG-800<\/a> Il s\u2019agit d\u2019un indicateur de configuration de l\u2019\u00e9quipement, et non d\u2019une preuve d\u2019une configuration particuli\u00e8re de la PF. V\u00e9rifiez le mode de l\u2019onduleur, le code du r\u00e9seau, la connexion du transformateur et les exigences de l\u2019entreprise avant de modifier la configuration cible.<\/p>\n<p>Tracez la tendance de la valeur et de la magnitude au cours d'un cycle de fonctionnement complet. Une usine peut \u00eatre \u00e0 l'arr\u00eat pendant la production, \u00e0 pleine capacit\u00e9 au moment de la charge maximale et en marche pendant les pauses lorsque les \u00e9tages de condensateur restent connect\u00e9s. Archivez les donn\u00e9es d'intervalles de stockage avec l'\u00e9tat du contr\u00f4leur afin que toute variation de signe puisse \u00eatre expliqu\u00e9e. Une seule lecture point par point n'est pas suffisante pour dimensionner ou r\u00e9gler un syst\u00e8me de correction.<\/p>\n<p>V\u00e9rifiez la mesure \u00e0 la fois au niveau du transformateur de charge et au niveau de la ligne principale lorsque l\u2019installation comporte plusieurs points de compensation. Une batterie de condensateurs locale peut rendre l\u2019alimentation \u00e9lectrique tr\u00e8s performante, tandis qu\u2019une autre batterie de condensateurs importera de l\u2019\u00e9nergie r\u00e9active. Le compteur d\u2019\u00e9lectricit\u00e9 peut afficher le r\u00e9sultat net \u00e0 un autre endroit. Marquez la position du CT et les limites de mesure sur le sch\u00e9ma \u00e0 une seule ligne.<\/p>\n<figure><img decoding=\"async\" alt=\"BWG-800 Photovoltaic Grid-Connected Cabinet shown as a product enclosure reference\" loading=\"lazy\" src=\"https:\/\/lbajiele.com\/wp-content\/uploads\/2026\/04\/BWG-800-Photovoltaic-grid-connected-cabinet.webp\"\/><figcaption>BWG-800 Photovoltaic Grid-Connected Cabinet reference image. Exterior appearance does not establish internal components, protection settings or project ratings.<\/figcaption><\/figure>\n<p>Les harmoniques peuvent distorter la forme d\u2019onde du courant, de sorte que le d\u00e9placement PF et le PF r\u00e9el diff\u00e8rent. Un groupe de condensateurs peut r\u00e9sonner avec l\u2019inductance de la source \u00e0 une fr\u00e9quence harmonique. Avant d\u2019ajouter des \u00e9tages ou de modifier les r\u00e9acteurs, utilisez un analyseur de qualit\u00e9 de l\u2019alimentation et un \u00e9tude harmonique. Des groupes d\u00e9phase\u00e9s, des filtres actifs ou des commandes d\u2019invers\u00e9 peuvent \u00eatre plus appropri\u00e9s qu\u2019un simple contacteur \u00e0 condensateur.<\/p>\n<figure><img decoding=\"async\" alt=\"YB27-12 Combined American Type Prefabricated Substation shown as a product enclosure reference\" loading=\"lazy\" src=\"https:\/\/lbajiele.com\/wp-content\/uploads\/2026\/04\/YB27-12-MODULAR-BOX-SUBSTATION-AMERICAN.webp\"\/><figcaption>YB27-12 Combined American Type Prefabricated Substation reference image. Exterior appearance does not establish internal components, protection settings or project ratings.<\/figcaption><\/figure>\n<p>Lorsque le compteur affiche un facteur de puissance positif inattendu, v\u00e9rifiez d\u2019abord la polarit\u00e9 du CT et la cartographie des phases, puis inspectez les contacteurs de condensateur et les r\u00e9glages de l\u2019onduleur. N\u2019alterez pas la valeur cible de facteur de puissance avant d\u2019avoir v\u00e9rifi\u00e9 la convention de signe et les c\u00e2blages avec un chargeur connu. Documentez la correction, les seuils d\u2019alarme et la r\u00e9ponse de maintenance dans le dossier de mise en service.<\/p>\n<p>Enfin, d\u00e9finissez une plage de fonctionnement maximale afin que le contr\u00f4leur ne change pas de phase de condensateur pour chaque petite variation. Incluez le temps de d\u00e9charge, le charge minimum et les limites d\u2019alarme dans le descriptif de commande. V\u00e9rifiez le seuil cible en regard des exigences de l\u2019utilit\u00e9 et des limites du fabricant de l\u2019\u00e9quipement plut\u00f4t que de choisir la valeur de PF la plus \u00e9lev\u00e9e \u00e0 tout moment.<\/p>\n<p>Notez les valeurs limites de cible, seuil de mort et alarme dans la documentation du panneau afin que le remplacement d\u2019un contr\u00f4leur futur ne modifie pas inaper\u00e7u le comportement de la phase de retard.<\/p>\n<h2>D\u00e9cisions de correction sp\u00e9cifiques au moteur<\/h2><p>La correction du retard de phase d\u2019un moteur peut r\u00e9duire la consommation de courant du chargeur et la charge du transformateur, mais la taille du condensateur doit correspondre au profil de fonctionnement r\u00e9el. Une correction excessive peut rendre le syst\u00e8me non stable lorsque le moteur est d\u00e9charg\u00e9 ou d\u00e9branch\u00e9. Ne connectez pas directement un condensateur \u00e0 une sortie de variateur de fr\u00e9quence. Suivez les recommandations du fabricant du variateur et les exigences de l\u2019\u00e9tude harmonique.<\/p><p>Pour un d\u00e9marreur de moteur, coordonnez la protection contre les surcharges, la fonction du contacteur, le passage des condensateurs et les r\u00e9glages du disjoncteur. Une batterie de condensateurs peut rester aliment\u00e9e m\u00eame apr\u00e8s que le moteur a d\u00e9marr\u00e9, \u00e0 moins que les d\u00e9charges et les interrupteurs de s\u00e9curit\u00e9 ne soient correctement con\u00e7us. V\u00e9rifiez la position du CT lorsque vous utilisez un contr\u00f4leur PF automatique.<\/p><p>Le facteur de puissance du moteur a \u00e9galement une incidence sur la dimensionnement du g\u00e9n\u00e9rateur et du transformateur. Un g\u00e9n\u00e9rateur doit fournir \u00e0 la fois la tension et le courant r\u00e9actif, tandis qu\u2019un transformateur est soumis \u00e0 une surchauffe due \u00e0 la puissance apparente. Incluez la tension de d\u00e9marrage et le PF de fonctionnement le plus faible dans l\u2019\u00e9tude de la source.<\/p><h2>Foire aux questions<\/h2>\n<div id=\"rank-math-faq\" class=\"rank-math-block\">\n<div class=\"rank-math-list\">\n<div id=\"faq-question-1\" class=\"rank-math-list-item\">\n<h3 class=\"rank-math-question\">What instrument should I use to test power factor?<\/h3>\n<div class=\"rank-math-answer\">\n\n<p>Use a power analyzer that measures real and apparent power with the correct voltage and current connections for the circuit. Current alone is insufficient.<\/p>\n\n<\/div>\n<\/div>\n<div id=\"faq-question-2\" class=\"rank-math-list-item\">\n<h3 class=\"rank-math-question\">How is power factor calculated from measured power?<\/h3>\n<div class=\"rank-math-answer\">\n\n<p>True power factor is real power divided by apparent power at the same circuit boundary. Confirm the analyzer\u2019s definitions, especially for distorted or unbalanced loads.<\/p>\n\n<\/div>\n<\/div>\n<div id=\"faq-question-3\" class=\"rank-math-list-item\">\n<h3 class=\"rank-math-question\">Why should current sensor direction be checked?<\/h3>\n<div class=\"rank-math-answer\">\n\n<p>Reversed sensors or incorrect channel mapping can alter measured power signs. Compare the connections with the instrument manual before interpreting reverse flow or leading and lagging indications.<\/p>\n\n<\/div>\n<\/div>\n<div id=\"faq-question-4\" class=\"rank-math-list-item\">\n<h3 class=\"rank-math-question\">Is motor efficiency the same as power factor?<\/h3>\n<div class=\"rank-math-answer\">\n\n<p>No. Efficiency compares mechanical output with real electrical input. Power factor compares real electrical input power with apparent electrical input power.<\/p>\n\n<\/div>\n<\/div>\n<div id=\"faq-question-5\" class=\"rank-math-list-item\">\n<h3 class=\"rank-math-question\">Which operating conditions should a power-factor report include?<\/h3>\n<div class=\"rank-math-answer\">\n\n<p>Record the measurement boundary, load state, time interval, voltage and current configuration, sensor ratios, sign convention, and whether the reading is true or displacement power factor.<\/p>\n\n<\/div>\n<\/div>\n<\/div>\n<\/div>","protected":false},"excerpt":{"rendered":"<p>To test power factor, measure real electrical input power and apparent input power at the same circuit boundary with a correctly configured power analyzer. Power factor is P\/S; motor efficiency is mechanical output power divided by real electrical input power. These are different quantities. Record the operating load, analyzer configuration, voltage\/current channel mapping and the [&hellip;]<\/p>\n","protected":false},"author":6,"featured_media":3942,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[53],"tags":[76,83],"class_list":["post-3843","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-switchgear-protection","tag-medium-voltage-switchgear","tag-power-distribution"],"blocksy_meta":[],"acf":[],"_links":{"self":[{"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/posts\/3843","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/users\/6"}],"replies":[{"embeddable":true,"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/comments?post=3843"}],"version-history":[{"count":7,"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/posts\/3843\/revisions"}],"predecessor-version":[{"id":4011,"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/posts\/3843\/revisions\/4011"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/media\/3942"}],"wp:attachment":[{"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/media?parent=3843"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/categories?post=3843"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/lbajiele.com\/fr\/wp-json\/wp\/v2\/tags?post=3843"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}