S□ – M Oil-Immersed Power Transformer

The S□-M series three-phase oil-immersed power transformers are state-of-the-art national innovative technical products, developed based on optimized structural design for modern power equipment.

Overview

The core design philosophy prioritizes product reliability and enhanced performance. During development, we recalibrated loss parameters and structural configurations in accordance with practical operating conditions of modern power equipment, so that calculated loss figures closely match measured test values.

The product adopts optimized structural design with a well-balanced copper-to-iron material ratio, which minimizes raw material costs while delivering a more compact and rational mechanical structure.

Technical Parameters

Rated
Capacity
(kVA)
Voltage Combination
And Tap Range
Vector
Group
No
Load
Loss(W)
Load
Loss(W)
No
Load
Current
(%)
Short
Circuit
Impedance
(%)
Overall Size(mm) Gauge Weight
(kg)
High
Voltage
(kV)
Tap
Range
±%
Low
Voltage
(kV)
Length
(L)
Width
(VV)
Height
(H)
Horizx
Vert
ax b
30 6
6.3
10
10.5
11
±5%
±2×2.5%
0.4 Dyn11
Yyno
100 630/600 1.5 4.0% 690 510 920 400×400 275
50 130 910/870 1.3 730 510 960 400×450 340
63 150 1090/1040 1.2 750 550 1000 400×450 385
80 180 1310/1250 1.2 790 620 1020 400×450 450
100 200 1580/1500 1.1 790 700 1040 550×550 520
125 240 1890/1800 1.1 840 800 1070 550×550 625
160 280 2310/2200 1.0 1070 670 1130 550×550 695
200 340 2730/2600 1.0 1140 750 1140 550×550 795
250 400 3200/3050 0.9 1200 800 1190 550×550 955
315 480 3830/3650 0.9 1300 860 1210 550×550 1085
400 570 4520/4300 0.8 1380 900 1240 660×660 1290
500 680 5410/5100 0.8 1450 950 1300 660×660 1590
630 810 6200 0.6 4.5% 1500 970 1360 660×660 1850
800 980 7500 0.6 1660 1140 1400 660×660 2210
1000 1150 10300 0.6 1690 1190 1530 660×660 2570
1250 1360 12000 0.5 1760 1230 1600 820×820 3115
1600 1640 14500 0.5 1800 1250 1660 820×820 3520
2000 1940 18300 0.4 5.0% 2070 1270 1880 820×820 4375
2500 2290 21200 0.4 2180 1320 1970 820×820 4950

Note 1: For transformers rated 500 kVA and below, load loss figures above the slash apply to Dyn11 or Yzn11 vector groups, while those below the slash correspond to the Yyn0 vector group.

Note 2: When the transformer’s annual average load factor ranges from 35% to 40%, the loss values listed in the table deliver maximum operational efficiency.

Frequently Asked Questions

What types of transformers do you manufacture?

LBAJI manufactures various transformers, including:

  • Oil Immersed Distribution Transformers
  • Dry Type Transformers
  • Cast Resin Transformers
  • Power Transformers
  • Solar Step-up Transformers

Our transformers are widely used in:

  • Industrial plants
  • Solar farms
  • Commercial buildings
  • Mining projects
  • Infrastructure projects
What voltage levels can your transformers support?

Our transformers can be designed according to different project requirements.

Typical voltage ranges include:

  • Low Voltage: 0.4kV
  • Medium Voltage: 6kV, 10kV, 11kV, 20kV, 22kV, 33kV
  • Higher voltage levels available upon request

The transformer rating can also be customized according to project capacity requirements.

What is the difference between oil immersed transformers and dry type transformers?

Oil Immersed Transformers

Advantages:

  • Higher capacity range
  • Better cooling performance
  • Suitable for outdoor applications
  • Cost-effective for large projects

Applications:

  • Power grids
  • Industrial facilities
  • Solar farms

Dry Type Transformers

Advantages:

  • Fire resistant
  • Environmentally friendly
  • Low maintenance
  • Suitable for indoor installation

Applications:

  • Buildings
  • Hospitals
  • Data centers
  • Commercial facilities
What standards do your transformers comply with?

Our products can be manufactured according to international standards including:

  • IEC standards
  • IEEE standards
  • GB standards

Testing reports and technical documents can be provided according to project requirements.