35kV OIL-IMMERSED POWER TRANSFORMER

S □ -50-4000/35 oil-immersed transformer is suitable for AC 50Hz, rated working voltage 35kV power system, as a small and medium-sized substation transformer equipment.

Catégorie :

Model Meaning

Scope Of Application

S □ -50-4000/35 oil-immersed transformer is suitable for AC 50Hz, rated working voltage 35kV power system, as a small and medium-sized substation transformer equipment.

Iron Core

The core is cold rolled silicon steel sheet with high permeability magnetic grain orientation. The iron core is a conventional iron core,an all-oblique joint stacking type iron core, the iron core column is a multi-step circular cross-section, and the iron yoke and the iron core are equal cross-section.

Winding

The windings are concentric coils; The high voltage winding has a tap required for the tapping voltage, which is led to the tap-changer. The switch is installed on the box cover, and the tapping voltage can be changed only after the power supply is cut off.

Safety Protection Device

The transformer is equipped with a gas relay and a pressure relief valve.

Oil Protection Device

The transformers are all equipped with oil conservators, and one end is equipped with an oil level gauge;A moisture absorber with oil seal should be installed on the transformer oil conservator;

Oil Temperature Measuring Device

The transformers are all equipped with a glass thermometer tube holder. The tube holder is located on the top of the oil tank and extends into the oil by 120±10m;

Transformers of 10000kVA and above are equipped with outdoor signal thermometers;

Technical Parameters

35kV three-phase power transformer S □

model Rated
Capacity
(KVA)
Rated Voltage (kV) connection
groups
Loss(W) no-load
current
(%)
impedance
voltage
(%)
weight (kg)
high
pressure
(kV)
low
pressure
(kV)
no-load load oil weight total weight
S11-50/35 50 35±5% 0.4 Yyn0 210 1210 1.8 6.5 320 1090
S11-100/35 100 290 2020 1.62 378 1160
S11-125/35 125 340 2380 1.56 330 1250
S11-160/35 160 360 2830 1.48 420 1290
S11-200/35 200 430 3300 1.39 460 1480
S11-250/35 250 510 3960 1.26 500 1650
S11-315/35 315 610 4760 1.26 520 1720
S11-400/35 400 733 5760 1.16 670 2130
S11-500/35 500 860 6900 1.16 690 2360
S11-630/35 630 1040 8280 1.1 750 2760

35kV Three-Phase Power Transformer

model Rated
Capacity
(KVA)
Rated Voltage (kV) connection
groups
Loss(W) no-load
current
(%)
impedance
voltage
(%)
weight (kg)
high
pressure
(kV)
low
pressure
(kV)
no-load load oil
weight
total
weight
Add oil
weight
Transport
weight
S11-800/35 800 35±5% 10.5
6.3
3.15
Yd11 1.23 9.9 0.9 6.5 0.88 3.83
S11-1000/35 1000 1.44 12.1 0.9 6.5 0.98 4.3 4.01
S11-1250/35 1250 1.76 14.6 0.81 6.5 1.02 4.64 4.24
S11-1600/35 1600 2.12 17.5 0.76 6.5 1.18 5.12 4.61
S11-2000/35 2000 2.72 17.8 0.67 6.5 1.25 5.87 5.06
S11-2500/35 2500 3.2 20.7 0.67 6.5 1.39 6.97 5.91
S11-3150/35 3150 35±5%
38.5±5%
3.8 24.3 0.63 7 1.6 8.02 6.88
S11-4000/35 4000 4.52 28.8 0.63 7 1.9 9.27 7.59
S11-5000/35 5000 5.4 33 0.54 7 2.15 10.98 9.89
S11-6300/35 6300 35±
2×2.5%
38.5±
2×2.5%
11 Yd11 6.56 36.9 0.54 7.5 2.05 12.98 0.65 10.63
S11-8000/35 8000 10.5 9 40.5 0.49 7.5 2.5 14.02 0.69 11.54
S11-10000/35 10000 6.6 10.88 47.7 0.49 7.5 3.8 17.7 0.7 15.8
S11-12500/35 12500 6.3 12.6 56.7 0.45 8 3.86 18.58 0.93 16
S11-16000/35 16000 3.3 15.2 69.3 0.45 8 4.45 23.57 1.11 21.2
S11-20000/35 20000 3.15 18 83.7 0.45 8 6.36 29.7 1.57 26.11
S11-25000/35 25000 21.28 99 0.36 8 6.49 39.2 1.82 34.3
S11-31500/35 31500 25.28 118.8 0.36 8 6.69 43.1 2.02 37.1
S11-40000/35 40000 28.8 155.25 0.48 8 7.78 46.9 2.48 38.5

Note: The dimensions and weight provided are only for reference in the design and selection, and the final dimensions and weight are subject to our company’s product drawings.

35kV oil-immersed three-phase double -winding unexcited voltage regulation power transformer energy efficiency class

Rated Capacity
(KVA)
Level1 Level2 Level3 Short
Circuit
Impedance
(%)
no-load Loss load Loss (75°C) no-load Loss load Loss (75°C) no-load Loss load Loss (75°C)
3150 1.7 20.7 2 20.7 2.4 21.9 7
4000 2 24.6 2.3 24.6 2.9 25.9
5000 2.4 28.2 2.8 28.2 3.5 29.7
6300 2.9 31.5 3.4 31.5 4.2 33.3 8
8000 4 34.6 4.7 34.6 5.8 36.5
10000 4.8 40.8 5.7 40.8 7 43
12500 5.5 48.4 6.5 48.4 8 51.1
16000 6.7 59.2 7.9 59.2 9.7 62.5
20000 7.9 71.6 9.4 71.6 11.5 75.5
25000 9.4 84.6 11.1 84.6 13.6 89.3 10
21500 11.1 100.8 13.1 100.8 16.2 106.4

35kV oil-immersed three-phase double -winding on-load regulating power transformer energy efficiency class

Rated Capacity
(KVA)
Level1 Level2 Level3 Short
Circuit
Impedance
(%)
no-load Loss load Loss (75°C) no-load Loss load Loss (75°C) no-load Loss load Loss (75°C)
3150 1.8 22.2 2.1 22.2 2.6 23.5 7
4000 2.1 26.2 2.5 26.2 3.1 27.6
5000 2.6 30.8 3 30.8 3.7 32.5
6300 3.1 33 3.7 33 4.5 34.9 7.5
8000 4.3 36.5 5.1 36.5 6.3 38.6
10000 5.1 43.2 6 43.2 7.4 45.6
12500 6 51.1 7.1 51.1 8.7 54 8
16000 7.2 63.3 8.5 63.3 10.5 66.8
20000 8.5 74.4 10.1 74.4 12.4 78.6
25000 10.1 88 11.9 88 14.6 92.9 10
21500 12 104.4 14.2 104.4 17.4 110.2