Overview
KYN28A-12(Z) Indoor AC high-voltage metal-armored withdrawable switchgear (hereinafter referred to as “switchgear”) is suitable for three-phase AC 50Hz power systems and is used to receive and distribute electrical energy and to control, protect and monitor circuits.
This product complies with the following standards: GB3906 “3~35kV AC Metal-enclosed Switchgear”, GB/T11022 “Common Technical Requirements for High Voltage Switchgear and Controlgear”, and IEC60298 “AC Metal-enclosed Switchgear and Controlgear with Rated Voltage of 1kV and Above”.
Technical Parameter
| Item | Unit | Data | |
| Rated voltage | kV | 6, 7.2, 12 | |
| Rated frequency | Hz | 50 | |
| Rated current of circuit breaker | A | 630, 1250, 1600, 2000, 2500, 3150 | |
| Rated current of switchgear | A | 630, 1250, 1600, 2000, 2500, 3150 | |
| Rated short-time withstand current (4S) | kA | 20, 25, 31.5, 40 | |
| Rated peak withstand current (peak) | kA | 50, 63, 80, 100 | |
| Rated short-circuit breaking current | kA | 20, 25, 31.5, 40 | |
| Rated short-circuit closing current (peak value) | kA | 50, 63, 80, 100 | |
| Rated insulation level 1-minute power frequency withstand voltage |
Between the poles and between the poles and the earth | kV | 24, 32, 42 |
| Between fractures | kV | 24, 32, 42 | |
| Lightning impulse withstand voltage (peak value) |
Between the poles and between the poles and the earth | kV | 40, 60, 75 |
| Between fractures | kV | 46, 70, 85 | |
| Class of protection | The enclosure is IP4X, and when the compartments and circuit breaker compartment doors are open, they are IP2X. | ||






Reviews