Série de transformateurs secs à isolation en résine SC (B)

With these advantages, our dry-type transformers are widely used in power transmission and distribution systems, including hotels, restaurants, airports, high-rise buildings, commercial centers, residential communities, and other important facilities. They are also suitable for harsh environments such as subways, metallurgical plants, vessels, and offshore drilling platforms.

Overview

Our resin-insulated dry-type transformers are developed by our company based on advanced imported technologies, including the SC9/SCB9 series and SC10/SCB10 series fillerreinforced thin-insulation dry-type transformers. Since the windings are fully encapsulated with epoxy resin, the transformers feature flame-retardant, fire-resistant, explosionresistant, maintenance-free, and environmentally friendly characteristics. They are compact in size and can be installed directly near load centers.Optimized structural design and vacuum casting technology result in low partial discharge, low noise, and excellent heat dissipation performance. Under forced-air cooling conditions, the transformers can operate continuously at 140% of rated load. Each transformer is equipped with an intelligent temperature controller featuring fault alarm, over-temperature alarm,over-temperature trip, and event recording functions. The controller communicates with computers via an RS485 serial interface, enabling centralized monitoring and control.

Ralated Standards & Parameters

◆GBT10228-2015,GB1094.11-2007,GB 20052-2020,JBT10088-2004,GB4208-1993

◆Rated high voltage: 10 (11,10.5,6.6,6.3,6) KV

◆Rated low voltage: 0.4KV

◆Vector Group: Dyn11 or Yyn0

◆High voltage tap range: ± 5 or ± 2X2.5%

◆Insulation level: LI75AC35/LI0AC5

◆Frequency: 50Hz

Technical Parameters of 10 kV Class SC(B)11 Series Epoxy Resin Insulated Dry-Type Transformers 6 kV, 10 kV Class 30 kVA ~ 2500 kVA Off-Circuit Tap-Changing Distribution Transformers

Classé
capacity
(kVA)
Combinaison de tensions
and tap range (kV)
Vector
Group
No-load
Loss
(KW)
Load-Loss at Different Insulation Temperatures(kW) No-load
current
(%)
Short
circuit
impedance
(%)
Poids
(kg)
Overall Dimensions
(mm)
(L×W×H)
Installation
Dimensions
(mm)
With
Enceinte
Dimensions
(L×W×H)
(mm)
Haut
voltage
(kV)
Tap
Range
±%
Basse tension
(kV)
130℃(B,100K) 155℃(F,120K) 80℃(H,145K)
30 6
6.3
6.6
10
10.5
11
±2.5
±5
0.4 Dyn11
Yyn0
0.17 0.67 0.71 0.76 2 4 270 590×500×640 400/400 1000×900×2200
50 0.24 0.94 1 1.07 2 360 620×550×670 400/400 1000×900×2200
80 0.33 1.29 1.38 1.48 1.5 510 680×580×710 400/450 1050×950×2200
100 0.36 1.48 1.57 1.69 1.5 570 720×600×720 400/450 1100×950×2200
125 0.42 1.74 1.85 1.98 1.3 600 860×650×850 550/550 1250×1000×2200
160 ±2×2.5
±5
0.48 2 2.13 2.28 1.3 730 900×710×890 550/550 1300×1050×2200
200 0.56 2.37 2.53 2.71 1.1 850 940×750×980 550/660 1300×1100×2200
250 0.65 2.59 2.76 2.96 1.1 960 960×770×1030 660/660 1300×1100×2200
315 0.79 3.27 3.47 3.73 1 1130 1020×790×1060 660/660 1400×1150×2200
400 0.88 3.75 3.99 4.28 1 1330 1060×880×1100 660/820 1450×1200×2200
500 1.04 4.59 4.88 5.23 1 1480 1080×900×1160 660/820 1450×1200×2200
630 1.17 5.61 5.96 6.4 0.85 6 1580 1200×920×1150 820/820 1550×1200×2200
800 1.37 6.55 6.96 7.46 0.85 1910 1260×920×1260 820/820 1600×1200×2200
1000 1.59 7.65 8.13 8.76 0.85 2260 1320×940×1300 820/820 1700×1250×2200
1250 1.88 9.1 9.69 10.3 0.85 2660 1380×950×1380 820/820 1750×1250×2200
1600 2.2 11 11.7 12.5 0.85 3180 1460×1120×1490 1070/1070 1850×1400×2200
2000 2.75 13.6 14.4 15.5 0.7 3600 1490×1120×1620 1070/1070 1900×1450×2200
2500 3.24 16.1 17.1 18.4 0.7 4220 1520×1120×1760 1070/1070 1950×1500×2200
3150 4.62 / 22.5 / 0.6 5000 1600×1120×1860 1070/1070 2000×1550×2200
4000 5.36 1 27 / 0.6 6300 1680×1120×2150 1070/1070 2100×1600×2200

Foire aux questions

Quels types de transformateurs fabriquez-vous ?

LBAJI fabrique divers transformateurs, notamment :

  • Transformateurs de distribution immergés dans l'huile
  • Transformateurs de type sec
  • Transformateurs en résine coulée
  • Transformateurs de puissance
  • Transformateurs élévateurs solaires

Nos transformateurs sont largement utilisés dans :

  • Usines industrielles
  • Parcs solaires
  • Bâtiments commerciaux
  • Projets miniers
  • Projets d'infrastructure
Quels niveaux de tension vos transformateurs peuvent-ils supporter ?

Nos transformateurs peuvent être conçus en fonction des différentes exigences du projet.

Les plages de tension typiques comprennent :

  • Basse tension : 0,4 kV
  • Moyenne tension : 6kV, 10kV, 11kV, 20kV, 22kV, 33kV
  • Niveaux de tension supérieurs disponibles sur demande

La puissance nominale du transformateur peut également être personnalisée en fonction des exigences de capacité du projet.

Quelle est la différence entre les transformateurs immergés dans l'huile et les transformateurs de type sec ?

Transformateurs immergés dans l'huile

Avantages :

  • Plage de capacité supérieure
  • Meilleures performances de refroidissement
  • Convient pour les applications extérieures
  • Rentable pour les grands projets

Applications :

  • Réseaux électriques
  • Installations industrielles
  • Parcs solaires

Transformateurs de type sec

Avantages :

  • Résistant au feu
  • Respectueux de l'environnement
  • Peu exigeant
  • Convient pour une installation à l'intérieur

Applications :

  • Bâtiments
  • Hôpitaux
  • Centres de données
  • Installations commerciales
Quelles sont les normes auxquelles vos transformateurs sont conformes ?

Nos produits peuvent être fabriqués selon les normes internationales, notamment :

  • Normes CEI
  • Normes IEEE
  • Normes GB

Des rapports de test et des documents techniques peuvent être fournis en fonction des exigences du projet.