S□-M-L Transformeur Delta Tridimensionnel

The solid core oil- immersed transformer is an efficient and energy-saving transformer using traditional material, but the operation noise is lower and the structure is more compact. Its excellent performance in reducing loss and saving materials is fully in line with China’s energy-saving policy.

Overview

The solid core oil- immersed transformer is a new type of high reliability transformer with reasonable structure, better performance and lower manufacturing cost.

The product breaks through the traditional flat structure and adopts three-phase symmetrical three-dimensional structure. And because there is no air gap in the magnetic circuit, the magnetic direction of the silicon steel strip is completely consistent with the direction of the magnetic circuit, the three core columns are arranged in an equilateral triangle three-dimensional the three magnetic circuits are the same length, and are the shortest, and the processing kit is free of waste. Therefore, it is an efficient and energy-saving transformer using traditional material, but the operation noise is lower and the structure is more compact. Its excellent performance in reducing loss and saving materials is fully in line with China’s energy-saving policy.

Model Meaning

Product Characteristics

Energy saving and consumption reduction and noise reduction;

Save materials and reduce costs;

Three-phase balance, enhanced short-circuit resistance;

Stable quality and improved production efficiency;

Anti-theft, small area and beautiful appearance;

Good economy and high cost performance.

Appearance and installation dimensions

S11-M.L Series Three-Dimensional Delta Transformer

S13-M.L Series Three-Dimensional Delta Transformer

Overall Size Of Terminal

S11-M.L Series Three-Dimensional Delta Transformer

S13-M.L Series Three-Dimensional Delta Transformer

Paramètres techniques

S11-M.L Series Three-Dimensional Delta Transformers

Classé
Capacité
(KVA)
Rated Voltage(kV) connection
groups
Perte(W) no-load
current
(%)
impedance
voltage
(%)
weight (kg) Overall Size
haut
pressure
(kV)
bas
pressure
(kV)
no
load
load Heavy oil in
the body
oil
weight
total
weight
Length
(L)
width
(B)
height
(H)
30 10
± 5%10
±
2×2.5%
0.4 Dyn11
Yzn11
Yyn0
100 630/600 0.33 4 167 107 358 358 677 1159
50 130 910/870 0.3 4 222 113 423 423 683 1224
80 180 1310/1250 0.27 4 278 153 525 525 727 1314
100 200 1580/1500 0.26 4 278 149 554 554 995 1314
160 280 2310/2200 0.24 4 439 168 746 746 905 1376
200 340 2730/2600 0.23 4 509 197 856 856 944 1394
250 400 3200/3050 0.22 4 591 228 986 986 965 1397
315 480 3830/3650 0.21 4 679 252 1124 1124 1031 1422
400 570 4520/4300 0.21 4 818 303 1340 1340 1060 1477
500 680 5410/5100 0.2 4 964 375 1618 1618 1207 1562
630 810 6200 0.2 4.5 1128 417 1939 1939 1270 1594
800 980 7500 0.19 4.5 1424 526 2417 2417 1360 1636
1000 1150 10300 0.18 4.5 1660 645 2955 2955 1510 1656
1250 1360 12000 0.17 4.5 1802 630 3135 3135 1525 1768
1600 1640 14500 0.16 4.5 2255 781 3784 3784 1510 1928
2000 2250 18500 0.15 4.5 3166 1239 5637 5637 1699 1863
2500 2400 24000 0.15 5 3158 1541 6089 6089 1762 2088

S13-M.L Series Three-Dimensional Delta Transformers

Classé
Capacité
(KVA)
Rated Voltage(kV) connection
groups
Perte(W) no-load
current
(%)
impedance
voltage
(%)
weight (kg) /Overall Size
haut
pressure
(kV)
bas
pressure
(kV)
no
load
load Heavy oil in
the body
oil
weight
total
weight
Length
(L)
width
(B)
height
(H)
30 10
±
5%10
±
2×2.5%
0.4 Dyn11
Yzn11
Yyn0
80 630/600 0.3 4 178 113 377 1028 682 1199
50 100 910/870 0.24 4 236 111 435 1025 683 1224
80 130 1310/1250 0.22 4 313 146 553 1096 722 1314
100 150 1580/1500 0.21 4 356 148 607 1096 722 1334
160 200 2310/2200 0.19 4 484 185 797 1080 935 1441
200 240 2730/2600 0.18 4 556 228 937 1109 960 1444
250 290 3200/3050 0.17 4 655 263 1091 1196 1036 1457
315 340 3830/3650 0.16 4 769 274 1269 1276 1105 1467
400 410 4520/4300 0.16 4 896 323 1437 1306 1131 1542
500 480 5410/5100 0.16 4 1044 433 1872 1483 1284 1592
630 570 6200 0.15 4.5 1352 414 2085 1395 1210 1649
800 700 7500 0.15 4.5 1613 496 2481 1526 1321 1711
1000 830 10300 0.14 4.5 1703 656 3000 1717 1487 1726
1250 970 12000 0.13 4.5 2065 702 3449 1711 1482 1829
1600 1170 14500 0.12 4.5 2592 1045 4459 1880 1628 1938

Note: The load loss values above the slash in the table are applicable to Dyn11 or Yzn11 connection groups, and the load loss values below the slash are applicable to Yyn0 connection groups.

Note: The overall size and weight provided are only for reference during design and selection. The final size and weight shall be subject to our company’s product drawings.

Outline Size

S11-M.L Series Three-Dimensional Delta Transformer

Capacité nominale
(KVA)
Installation size Low voltage phase terminal Low voltage 0 wire terminal
E1 E2 D Graphics b b1 d f Graphics b b1 d f
30 380 550 550 19 35 26 12.5 8 2 35 26 12.5 8
50 380 550 550 19 35 26 12.5 8 2 35 26 12.5 8
80 380 550 550 19 35 26 12.5 8 2 35 26 12.5 8
100 380 550 550 19 35 26 12.5 8 2 35 26 12.5 8
160 400 660 660 19 35 26 12.5 8 2 35 26 12.5 8
200 400 660 660 19 35 26 12.5 8 2 35 26 12.5 8
250 400 660 660 19 46 26 12.5 10 3 46 26 12.5 10
315 550 820 820 19 46 26 12.5 10 3 46 26 12.5 10
400 550 820 820 19 46 26 12.5 10 3 46 26 12.5 10
500 550 820 820 19 80 45 14.5 13 4 80 45 14.5 13
630 550 820 820 19 80 45 14.5 13 4 80 45 14.5 13
800 550 820 820 19 80 45 14.5 13 4 80 45 14.5 13
1000 550 1070 1070 19 90 45 18 17 4 80 45 18 17
1250 550 1070 1070 19 100 45 18 17 4 80 45 18 17
1600 550 1070 1070 19 100 45 18 17 4 100 45 18 17
2000 600 1300 1300 19 100 45 18 17 4 100 45 18 17
2500 600 1300 1300 19 125 50 19 15 4 100 45 18 17

S13-M.L Series Three-Dimensional Delta Transformer

Capacité nominale
(KVA)
Installation size Low voltage phase terminal Low voltage 0 wire terminal
E1 E2 D Graphics b b1 d f Graphics b b1 d f
30 380 550 19 2 35 26 12.5 8 2 35 26 12.5 8
50 380 550 19 2 35 26 12.5 8 2 35 26 12.5 8
80 380 550 19 2 35 26 12.5 8 2 35 26 12.5 8
100 380 550 19 2 35 26 12.5 8 2 35 26 12.5 8
160 400 660 19 2 35 26 12.5 8 2 35 26 12.5 8
200 400 660 19 3 35 26 12.5 8 3 35 26 12.5 8
250 400 660 19 3 46 26 12.5 10 3 56 26 12.5 10
315 550 820 19 3 46 26 12.5 10 3 56 26 12.5 10
400 550 820 19 3 46 26 12.5 10 3 56 26 12.5 10
500 550 820 19 4 80 45 14.5 13 4 80 45 14.5 13
630 550 820 19 4 80 45 14.5 13 4 80 45 14.5 13
800 550 820 19 4 80 45 14.5 13 4 80 45 14.5 13
1000 550 1070 19 4 90 45 18 17 4 80 45 14.5 13
1250 550 1070 19 4 100 45 18 17 4 80 45 14.5 13
1600 550 1070 19 4 100 45 18 17 4 100 45 18 17

Foire aux questions

Quels types de transformateurs fabriquez-vous ?

LBAJI fabrique divers transformateurs, notamment :

  • Transformateurs de distribution immergés dans l'huile
  • Transformateurs de type sec
  • Transformateurs en résine coulée
  • Transformateurs de puissance
  • Transformateurs élévateurs solaires

Nos transformateurs sont largement utilisés dans :

  • Usines industrielles
  • Parcs solaires
  • Bâtiments commerciaux
  • Projets miniers
  • Projets d'infrastructure
Quels niveaux de tension vos transformateurs peuvent-ils supporter ?

Nos transformateurs peuvent être conçus en fonction des différentes exigences du projet.

Les plages de tension typiques comprennent :

  • Basse tension : 0,4 kV
  • Moyenne tension : 6kV, 10kV, 11kV, 20kV, 22kV, 33kV
  • Niveaux de tension supérieurs disponibles sur demande

La puissance nominale du transformateur peut également être personnalisée en fonction des exigences de capacité du projet.

Quelle est la différence entre les transformateurs immergés dans l'huile et les transformateurs de type sec ?

Transformateurs immergés dans l'huile

Avantages :

  • Plage de capacité supérieure
  • Meilleures performances de refroidissement
  • Convient pour les applications extérieures
  • Rentable pour les grands projets

Applications :

  • Réseaux électriques
  • Installations industrielles
  • Parcs solaires

Transformateurs de type sec

Avantages :

  • Résistant au feu
  • Respectueux de l'environnement
  • Peu exigeant
  • Convient pour une installation à l'intérieur

Applications :

  • Bâtiments
  • Hôpitaux
  • Centres de données
  • Installations commerciales
Quelles sont les normes auxquelles vos transformateurs sont conformes ?

Nos produits peuvent être fabriqués selon les normes internationales, notamment :

  • Normes CEI
  • Normes IEEE
  • Normes GB

Des rapports de test et des documents techniques peuvent être fournis en fonction des exigences du projet.